White Rodgers 1F86-0244 Manual De Usuario

Descargar
Página de 16
5
Menu 
Reference 
Number
Press
Key
Displayed 
(Factory
Default)
Press 
 or 
 
to select from 
listed options
Comments
6
 and 
L
(On)
OFF
Select Display Light On or OFF
7
 and 
Temp
(0 HI)
4 LO to 
4 HI
Select temperature display adjustment higher or 
lower
8
 and 
o
F
o
C
Select 
o
F / 
o
C Display (temperature units in Fahren-
heit or Celsius)
9
 and 
Change Filter
(OFF)
On
Select filter replacement indicator OFF or On
 and 
Change Filter
(200 h)
25 to 1975
If Change Filter selected On, selects time interval for 
Change Filter Indicator. (in 25 hour increments)
10
 and 
Returns to normal operation
1)  System Configuration - Selects SS (Single Stage) or HP 
(Heat Pump) operating mode. Default configuration is SS. 
For Heat Pump operation choose HP.
2)  Select  CS  (Cool  Savings™)  -  With  Cool  Savings™ 
enabled,  the  thermostat  will  make  small  adjustments  to 
the Setpoint temperature during periods of high demand 
to reduce cooling system running time and save energy. 
When the cooling system has been running for more than 
20 minutes, humidity in the home will be lower and a higher 
setpoint temperature will feel comfortable. After 20 minutes 
of run time, the thermostat will start increasing the setpoint 
temperature in steps of less than one degree as the system 
continues to run. These adjustments will eventually cause 
the system to satisfy the thermostat and turn the system 
off  to  reduce  the  energy  consumption.  When  the  Cool 
Savings  feature  is  active  and  making  adjustments,  the 
display will show “Save”. The amount of the adjustments to 
the setpoint temperature is dependent on the Cool Savings 
value that is set, 1 being the least adjustment and 6 being 
the  most  adjustment.  With  this  feature  set  to  OFF,  no 
change will occur when the cooling system is continuously 
running during the periods of high demand. Periods of high 
demand will normally occur during the late afternoon and 
early evening on the hottest days of the summer.
3 & 4) Select Cycle Rate Selection - The factory default setting 
for Single Stage Heat is Medium Cycle (ME). For Single 
Stage Cool the default setting is fast (FA). To change cycle 
rate, press the 
 and 
 buttons. 
  The cycle rate differentials for different settings are:
  MODE 
 
Fast 
Medium   Slow
   
 
 
(FA) 
  (ME)    (SL)
  SS Heat 
 
0.6°F    0.8°F    1.2°F
  SS Cool 
 
1.2°F       - 
  1.7°F
5)  Select Compressor Lockout CL OFF or ON - Selecting 
CL On will cause the thermostat to wait 5 minutes between 
cooling  cycles.  This  is  intended  to  help  protect  the 
compressor from short cycling. Some newer compressors 
already have a time delay built in and do not require this 
feature. Your compressor manufacturer can tell you if the 
lockout feature is already  present  in  their system. When 
the thermostat compressor time delay occurs, it will flash 
the setpoint for up to five minutes.
6)  Select Backlight Display - The display backlight improves 
display  contrast  in  low  lighting  conditions.  When  the  “C” 
terminal is connected, selecting backlight CdL On will keep 
the light on continuously. Select backlight OFF will turn the 
light on momentarily when any key is pressed. When the 
“C” terminal is not connected, regardless of the backlight 
selection, the light will be on momentarily when any key is 
pressed.
7)  Select Temperature Display Adjustment 4 LO to 4 HI - 
Allows you to adjust the room temperature display up to 4° 
higher or lower. Your thermostat was accurately calibrated 
at the factory but you have the option to change the display 
temperature  to  match  your  previous  thermostat.  The 
current or adjusted room temperature will be displayed on 
the display.
8)  Select F° or C° Readout - Changes the display readout to 
Celsius or Fahrenheit as required.
9) Select Filter Replacement Reminder and Set Run Time 
Select the “Change Filter” reminder On or OFF. If selected 
On, press 
 and 
 to select the time period from 25 to 
1975 hours in 25 hour increments. In a typical application, 
200 hours (default) of run time is approximately 30 days. 
After the selected time of blower operation, the thermostat 
will display “Change Filter” as a reminder to change or 
clean your air filter. When “Change Filter” is displayed, 
press  the 
  and 
  button  to  clear  the  display  and 
restart the time to the next filter change. A selection of OFF 
will cancel this feature.