White Rodgers 1E50N-301 Instruccion De Instalación

Descargar
Página de 4
Symptom 
Possible Cause 
Corrective Action 
 
No Heat/ No Fan 
1.  Blown fuse or tripped circuit breaker.      
Replace fuse or reset breaker.
(common problems) 
2.  Furnace power switch to OFF. 
Turn switch to ON. 
 
 
3.  Furnace blower compartment door or  
Replace door panel in proper position to engage
 
 
panel loose or not properly installed. 
safety interlock or door switch.  
No Heat 
1.  Pilot light not lit.                                
Re-light pilot. 
 
 
2.  Broken or melted anticipator wire. 
Excessive current or dead short in system. Have a qualifi ed service person check the system 
 
3.  Loose connection to thermostat 
before replacing thermostat.  
 
 
or system.  
Verify thermostat and system wires are securely attached. 
 
4.  Thermostat or heating system requires 
Your furnace manufacturer or service person can describe how to test the heating system to 
 
 
replacement or service.  
verify it is operating correctly. If the heating system is capable of operation and the no heat 
 
5.  System Switch not set to Heat. 
condition persists, replace the thermostat.
 
 
 
Set System Switch to Heat and raise temp above room temp.
Intermittent Heat 
1.  Furnace Lock-Out Condition 
Many furnaces have safety devices that shut the system down when a lock-out condition occurs. 
 
 
 
If the heat works intermittently contact the furnace manufacturer or local service person for  
 
 
 
 
assistance. 
    
Heat or Fan Runs 
1.  Possible short in wiring. 
Check each wire connection to the thermostat to verify it is neatly looped under the terminals. 
Constantly. 
2.  Possible short in thermostat.                       No extra wire should stick out from under the terminals. 
 
3.  Possible short in heat/cool/fan system. 
Furnace Cycles Too Fast  
See Step 5, Adjusting the Anticipator. 
The anticipation setting is the only adjustment that effects the heating cycle rate. If an accept-
or Too Slow Narrow or  
 
 
able cycle rate is not achieved using the anticipator contact a local service person for addi-
wide temperature swing 
    
tional suggestions. The location of the thermostat, size of the Heat/Cool System and current  
 
 
 
 
draw can infl uence the cycle rate.
Thermostat Setting and  
1.  Thermostat thermometer setting  
The thermometer can be adjusted by using a standard slotted screwdriver. Turn the thermom-
Thermostat Thermometer 
 
requires adjustment.  
eter pointer screw located inside the front cover to change the setting. For calibrating the  
Disagree 
2.  Thermostat setting lever requires  
setting lever contact a local heating and cooling service person. 
 
  
calibration.
Adjusting Thermometer   
1.  Thermostat thermometer disagrees  
The thermometer on the thermostat is accurately calibrated at our factory but you can adjust it 
 
 
with other room thermometers. 
by using a standard slotted screwdriver. Turn the thermometer pointer screw located inside 
 
 
 
the front cover to change the setting.
7
6
8
NEW THERMOSTAT  OPERATION
This thermostat is easy to operate. After power is turned on, use the system switch to 
select heating, or to turn the heating system off.
SPECIFICATIONS
ELECTRICAL DATA
Switch Rating
......................................  24 VAC (30 VAC max.)
Heating..................................................  0.15 to 1.2 Amps
Anticipator Rating:
Heating..................................................  Adjustable from 0.15 to 1.2 Amps
THERMAL DATA:
Temperature Range
.............................  50°F to 90°F (10°C to 32°C)
Operating Humidity Range.................  0 – 90% noncondensing
TROUBLESHOOTING
W
R
Heat
Anticipator
(adjustable)
Heating
System
24 VAC
120 VAC
Hot
Neutral
THERMOSTAT
SYSTEM
Figure 3. Typical wiring for single transformer heating system
www.white-rodgers.com
White-Rodgers is a division
of Emerson Electric Co.
The Emerson logo is a 
trademark and service mark
of Emerson Electric Co.
HOMEOWNER HELP LINE:  1-800-284-2925