Bradford-White Corp BWCH Manual De Usuario

Descargar
Página de 64
Page 11
COPPER BRUTE II (500 - 2000)
appliances. If assistance is required in determining 
how a blocked vent safety system should be connected 
to a Bradford White product, please call Applications 
Engineering at the Rochester phone number listed on 
back cover of this manual.
Refer to the installation and operating 
instructions on all appliances to be common vented 
for instructions, warnings, restrictions and safety 
requirements. If safe operation of all appliances 
connected to a common vent cannot be assured, 
including prevention of spillage of flue gasses into 
living spaces, common venting should not be applied, 
and appliances should each be vented separately.
2.2.4  Category III Vent
When the Copper Brute II is vented with 
horizontal discharge, it must be installed per 
this installation manual and the venting system 
manufacturer’s installation instructions. The vent 
system must be sealed stainless steel, per 
Table 5
.
Route the vent pipe to the heater as directly as 
possible. Seal all joints and provide adequate hangers 
as required in the venting system manufacturer’s 
Installation Instructions. Horizontal portions of the 
venting system must be supported to prevent sagging 
and may not have any low sections that could trap 
condensate. The unit must not support the weight of 
the vent pipe. Horizontal runs must slope downwards 
not less than ¼ inch per foot (2 cm/m) from the unit to 
the vent terminal. Reference 
Table 2
 for the size of the 
Category III vent system. Up to three elbows can be 
used with 50 linear feet (15.2m) of pipe. Subtract 10 
allowable linear feet (3.0m) for every additional elbow 
used.
 WARNING
The outdoor vent terminal gets hot. Unit must be 
installed in such a way as to reduce the risk of 
burns from contact with the vent terminal.
2.3  Locating Vent & Combustion Air 
Terminals
2.3.1  Side Wall Vent Terminal
The appropriate Bradford White side wall vent 
hood must be used, and is listed in the installation and 
operation manual.  The terminal provides a means of 
installing the vent piping through the building wall, 
and must be located in accordance with ANSI Z223.1/
NFPA 54 and applicable local codes.  In Canada, the 
installation must be in accordance with CSA B149.1 or 
.2 and local applicable codes.  Consider the following 
when installing the terminal:
1. 
Figure 3
 shows the requirements for mechanical 
vent terminal clearances for the U.S. and Canada.
2.  Vent terminals for condensing appliances or 
appliances with condensing vents are not 
permitted to terminate above a public walkway, 
or over an area where condensate or vapor could 
create a nuisance or hazard.
3.  Locate the vent terminal so that vent gases cannot 
be drawn into air conditioning system inlets.
4.  Locate the vent terminal so that vent gases cannot 
enter the building through doors, windows, 
gravity inlets or other openings.  Whenever 
possible, locations under windows or near doors 
should be avoided.
5.  Locate the vent terminal so that it cannot be 
blocked by snow.  The installer may determine 
that a vent terminal must be higher than the 
minimum shown in codes, depending upon local 
conditions.
6.  Locate the terminal so the vent exhaust does 
not settle on building surfaces or other nearby 
objects.  Vent products may damage such 
surfaces or objects.
7.  If the boiler or water heater uses ducted 
combustion air from an intake terminal located 
on the same wall, locate the vent terminal at least 
3 feet (0.9m) horizontally from the combustion 
air terminal, and locate the vent terminal at least 
1 foot (0.3m) above the combustion air terminal.
2.3.2  Side Wall Combustion Air Terminal
The Bradford White side wall combustion air 
terminal (listed in 
Table 2
) must be used when the 
unit takes its combustion air through a duct from a 
side wall. Consider the following when installing the 
terminal:
1.  Do not locate the air inlet terminal near a source 
of corrosive chemical fumes (e.g., cleaning fluid, 
chlorinated compounds, etc.)
2.  Locate the terminal so that it will not be subject 
to damage by accident or vandalism.
3.  Locate the combustion air terminal so that it 
cannot be blocked by snow. The National Fuel 
Gas Code requires that it be at least 12 inches (30 
cm) above grade, but the installer may determine 
it should be higher, depending upon local 
conditions.
4.  If the Copper Brute II is side-wall vented to the 
same wall, locate the vent terminal at least 3 
feet (0.9m) horizontally from the combustion air 
terminal, and locate the vent terminal at least 1 
foot (0.3m) above the combustion air terminal 
(
see Figure 3
).
 
TERM 
DESCRIPTION 
 
Pipe 
Must comply with UL Standard 1738 
 
 
such as Type 29-4C Stainless Steel 
 
 
(either insulated or non-insulated).
 
Joint 
Follow vent manufacturer’s instructions
   Sealing
Table 5. Required Horizontal Venting Material.