Bradford-White Corp TG-180I-N(X) Manual De Usuario

Descargar
Página de 92
67 
 
Code 
Code Description 
Remedy 
72 
Flame Sensing Device 
Fault 
Ensure flame rod is touching flame when unit fires. 
Check all wiring to flame rod for damage. 
Remove flame rod and check for carbon build-up; clean with sand paper. 
Check inside burner chamber for any foreign material blocking flame at flame rod. 
Measure micro amp output of sensor circuit with flame present. 
Replace flame rod. 
LC 
Scale Build-up in Heat 
Exchanger (when 
checking maintenance 
code history, “00” is 
substituted for “LC”) 
Flush heat exchanger.  Refer to instructions in manual. 
Replace heat exchanger. 
NOTE: The LC code is the only error code that will allow the unit to keep running.  The 
display will alternate between the LC code and the temperature setting.  The controller 
will continue to beep.  The LC code will reset if power is turned off and then on. 
No 
code 
Nothing happens 
when water flow is 
activated. 
Clean inlet water supply filter. 
On new installations ensure hot and cold water lines are not reversed. 
Check for bleed over. Isolate unit from building by turning off hot water line to building.  
Isolate the circulating system if present.  Open your pressure relief valve; if water is 
flowing, there is bleed over in your plumbing. 
Ensure you have at least the minimum flow rate required to fire unit. 
Ensure turbine spins freely. 
Measure the resistance of the water flow control sensor. 
Check for DC shorts at components. 
 
 
If any of the above diagnostic codes are seen flashing on the display, call for service. 
 
 
WARNING
 
Failure to remedy faults may result in severe burns, scalds, and/or death.