SERVICE PROCEDURE MCE-VI
High Limit (ECO)  Testing
Page 20
High Limit Control (ECO) Testing for
Contactor Models
1. Determine if Hi-Limit has actuated. This can be done by simply
depressing the reset buttons. If you hear and/or feel
 a small click, the switch has actuated.
2. Use caution and turn power on to water heater and observe
 heating cycle following the Hi-Limit Heating Cycle flow chart.
Switch Contacts:
Normally closed.
Open on rise @ 196°F ±4°F
Manual Reset.
DANGER
High voltage exposure. To avoid
hazard to Life or property, be sure
power is turned OFF to water heater
while performing this procedure.
N
Is water temp
over 196°F
N
Observe heating cycle.
Does switch open?
Switch OK
Is water temp
over 196°F
Replace switch
N
Y
Y
1.
STOP, DANGER! Turn power “OFF” to water heater.
2. Water temperature must be below 196°F ±4°F
3. Remove Hi-Limit switch from control panel. It is not necessary
 to remove immersion bulb from tank at this time. See
 general controls layout on page 4 for location.
4. Disconnect wire leads to Hi-Limit Control during this test.
5. Depress reset buttons to insure switch contacts are closed.
6. Set multi-meter to Ohms setting, Check continuity Thru circuit A & B as shown in the illustrations below.
- Continuity
IS present, Switch is okay.
- Continuity
NOT present, Replace switch.
High Limit Control Continuity Testing for
Contactor Models
High Limit Heating Cycle Flow Chart
NOTE
Disconnect
Wire Leads to Control
Circuit “A” Continuity Testing
Circuit “B” Continuity Testing
Y