Bradford-White Corp ULTRA HIGH EFFICIENCY COMMERCIAL GAS WATER HEATER Manual De Usuario

Descargar
Página de 76
16 
Approximate Time/Temperature Scald Chart 
 
 
 
 
 
 
 
Table 2. 
ALTERNATE SPACE HEATING WATER CONNECTIONS 
 
 
DANGER
 
Toxic chemical, such as those used for boiler treatment, must not be introduced into potable water used for space 
heating. 
This water heater must not be connected to an existing heating system or component(s) previously used with a non-
potable water heating appliance. 
All piping components connected to this water heater for space heating applications must be suitable for use with 
potable water. 
 
 
WARNING
 
When the system requires water for space heating at temperatures higher than required for other means, an ASSE 
approved mixing valve must be installed to temper the water for those uses in order to reduce the scald hazard potential. 
Failure to properly pipe this water heater may result in improper operation and damage to the water heater or structure. 
Oxygen contamination of this water heater will cause corrosion of iron and steel components, and can lead to water 
heater failure.   
 
Connect the system supply and return piping to the water heater.   
 
Refer to Figure 9 and Figure 10 for installation examples.  Maintain a minimum 1/2” clearance from hot water piping to 
combustible materials. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Figure 9.  Alternate Space Heating Connections 
APPROXIMATE TIME/TEMPERATURE RELATIONSHIPS IN SCALDS 
120°F (49°C) 
More than 5 minutes 
125°F (52°C) 
1½ to 2 minutes 
130°F (54°C) 
About 30 seconds 
135°F (57°C) 
About 10 seconds 
140°F (60°C) 
Less than 5 seconds 
145°F (63°C
Less than 3 seconds 
150°F (66°C) 
About 1½ seconds 
155°F (68°C) 
About 1 second