Bradford-White Corp ULTRA HIGH EFFICIENCY COMMERCIAL GAS WATER HEATER Manual De Usuario

Descargar
Página de 76
69 
Error 
Code 
Definition of Code 
Cause of Problem and Actions Taken to Correct 
62 
Maximum Number of 
Retries Detected 
Burner is either not lighting or not staying lit during ignition cycle.  Check inlet 
gas pressure for minimum pressure on rating label.  Can you hear sparking to 
the burner?  Check high voltage cable connections.  Check inlet gas pressure 
to the gas valve making sure the pressure is within the limits specified on the 
rating label.  Check gas valve wire harness for broken wires or shorts.  Check 
outlet gas pressure.  If 24 volts is present to the terminals at the gas valve, 
replace gas valve.  Check for voltage output to the blue gas valve wires on the 
control board pins.  If during the ignition trial period, there is no voltage present 
at the control board pin terminals for the blue wires leading to the gas valve, 
then replace the control board.   Replace spark rod if insulator is damaged or 
rod is loose.  Check to make sure combustion blower is operating when 
thermostat calls for heat.  If blower is not running check for 120 volts to blower 
harness and then at blower pin connections.  Replace control, wire harness, or 
blower if defective.  Check to make sure vent terminals are clear of debris or 
snow and ice.  Make sure the condensate drain flows freely. 
63 
Maximum Number of 
Ignition Recycles 
Detected 
Burner flame is lost during run cycle, then re-established on ignition cycle.  
Check inlet gas pressure.  Is gas pressure dropping below the minimum 
operating pressure on the rating label after the gas valve opens?  Is the gas 
pipe size to the water heater adequate?  Check the condition of the burner.  
Clean or replace as needed.  Check the burner flame and observe the 
microamp output on the run cycle.  Replace burner if clogged with dirt and 
debris.  Replace spark rod or flame sensor if damaged.  Check to make sure 
vent terminals are clear of debris or snow and ice.  Make sure the condensate 
drain flows freely. 
64 
Electronics Failure 
Replace control board. 
65 
High Water 
Temperature (Over 
200°F (93°C)
Water temperature in tank has exceeded 200°F (93°C).  Check tank sensor.  
Make sure sensor is fully inserted into the well (clip on sensor wire secures 
sensor in place).  Check sensor reading.  If not within specifications, replace 
sensor.  If sensor and wire harnesses check O.K., replace control board.