Honeywell Gas Control Troubleshooting Chart
LED Status
Control Status
Probable Cause
Five flashes and 
three second pause
Thermostat/well sensor fault.
Gas Control electronic fault detected.
Seven flashes and 
three second pause
Eight flashes and 
three second pause
Standing pilot remains on while set 
point knob is in “OFF” position.
1. Damage to the temperature sensor.
2. Temperature sensor resistance out of 
range.
1. Control needs to be reset.
2. Control is wet or physically
damaged.
Pilot valve stuck in open position.
Service 
Procedure
1. See service 
procedure V
1. Reset Gas Control
2. Replace Gas
Control.
Replace Gas Control.
Flammable Vapor Ignition Resistant Water 
Heaters
Green LED Indicator
Observe green LED indicator on 
Gas Control. Error flash codes are 
displayed with a three second pause 
before repeating. Check and repair 
the system as noted in the 
troubleshooting table below.
5
Water leak detected by accessory 
module.
Six flashes and 
three second pause
Excessive amount of water in drain 
pan/water dam.
1. Check T&P valve
2. Check all water     
fittings.
3. Pressurize and leak 
test tank.
5