Honeywell Gas Control Troubleshooting Chart
LED Status
Control Status
Probable Cause
None (LED not on or 
flashing
Pilot assembly is not lit
1. If set point knob is in “PILOT” 
position then pilot flame is detected. 
Turn set point knob to desired setting. 
2. If the set point knob is already at 
the desired setting, the water heater is 
satisfied. 
One flash and three 
second pause
Two quick flashes 
and a three second 
pause
Gas control is calling for heat (no 
fault).
Two flashes and 
three second pause
Weak pilot signal detected. System will 
reset when pilot flame is sufficient.
.
Gas Control is not powered. Light pilot.
1. Gas Control is powered and waiting 
for the set point knob to be turned to a 
water temperature setting.
2. Water heater is satisfied and 
operating normally. 
Tank temperature below set point of 
thermostat. 
1. Thermopile failure
2. Unstable pilot
3. Pilot tube block or restricted.
Service 
Procedure
If the pilot will not stay 
lit replace pilot 
assembly. If problem 
persists replace Gas 
Control.
1. Adjust set point knob 
to desired setting. 
Normal operation. 
1. See service
procedure II
2. See service
procedure III
3. See service
procedure III
Flammable Vapor Ignition Resistant Water 
Heaters
Green LED Indicator
Observe green LED indicator on 
Gas Control. Error flash codes are 
displayed with a three second pause 
before repeating. Check and repair 
the system as noted in the 
troubleshooting table below.
Four flashes and 
three second pause
Excessive tank temperature. System 
must be reset.
1. Temperature sensor out of
calibration
2. Faulty Gas Control
1. See service
procedure V
2. See service
procedure V
4
LED on continuously
(Solid)
Set point knob has been recently 
turned to the “OFF” position. Wait 
until LED goes out before 
attempting to relight
Set point knob was turned to “OFF” 
position.
LED will go out and the 
control will function 
normally when the pilot 
is lit.