SECTION X:  MAINTENANCE 
 
 
DANGER
 
DO NOT ATTEMPT TO REPAIR GAS VALVE. 
DO NOT ATTEMPT TO REPAIR IGNITION MODULE. 
DO NOT ATTEMPT TO REPAIR VENTURI. 
DO NOT ATTEMPT TO REPAIR THERMOSTAT BOARD. 
DO NOT ATTEMPT TO REPAIR TRANSFORMER. 
DO NOT ATTEMPT TO REPAIR PRESSURE SWITCH. 
 
GENERAL 
 
KEEP APPLIANCE AREA CLEAR AND FREE FROM COMBUSTIBLE MATERIALS, GASOLINE AND OTHER 
FLAMMABLE VAPORS AND LIQUIDS. 
  
Water heater maintenance includes periodic tank flushing and cleaning, and removal of lime scale.  The unit should be inspected and 
adjusted to maintain proper combustion.  Refer to Table 5, “Suggested Maintenance Schedule”.  A periodic inspection of the venting 
system should be made. 
 
MAINTENANCE SCHEDULE 
 
Following are the instructions for performing some of the recommended maintenance.  Unit inspection and adjustment should be 
performed by a competent technician. 
 
Suggested Maintenance Schedule 
 
COMPONENT 
OPERATION 
INTERVAL 
REQUIRED 
Tank Sediment 
Removal Monthly Flushing 
Anode Rods 
Inspect 
Semi-Annually 
Replace as 
Required 
Relief Valve 
Check Operation Semi-Annually 
Proper 
Operation 
Blower 
Clean Inlet Screen  
As Required 
Soft Brush 
Vent & Air 
Intake System 
Inspect Every 
Months 
Joints should 
be sealed 
Ignition System 
Inspect 
Annually 
Clean of dust 
and dirt 
Vent Terminal 
Free of Shrubs & 
Debris 
Monthly 
Remove object 
that caused 
restriction 
Combustion 
System 
Inspect Monthly 
Confirm 
S-OP 
Condensate 
Line 
Inspect Monthly 
Remove 
restriction 
Table 5. 
FLUSHING WATER HEATER 
1.  Turn OFF the water heater electrical disconnect switch. 
2.  Open the drain valve and allow water to flow until it runs clean. 
3.  Close the drain valve when finished flushing. 
4.  Turn ON the water heater electrical disconnect switch.