DRAIN VALVE AND TANK ACCESS PANEL 
 
The water heaters are equipped with a ¾ inch drain valve. 
An access panel covers the cleanout opening in the tank, which is sealed by a gasket and cover.  
 
RELIEF VALVE 
 
At least twice a year, the temperature and pressure relief valve should be checked to ensure that it is in operating 
condition.  To check the relief valve, lift the lever at the end of the valve several times.  The valve should seat properly and 
operate freely. 
 
If water does not flow, remove and inspect for obstructions or corrosion.  Replace with a new valve of the recommended 
size as necessary.  A thorough inspection of the valve should be performed at least every three years by removing the 
temperature and relief valve from the tank.  Do not attempt to repair the valve, as this could result in improper operation 
and a tank explosion.  In areas with poor water conditions, it may be necessary to inspect the T&P valve more often than 
the recommended maintenance schedule 
 
    
CAUTION
 
Before manually operating the valve, make sure that a drain line has been attached to the valve to direct the discharge 
to an open drain.  Failure to take this precaution could mean contact with extremely hot water passing out the valve 
during this checking operation. 
 
If the temperature and pressure relief valve on the water heater discharges periodically or continuously, it may be due to 
thermal expansion of water in a closed water supply system, or, it may be due to a faulty relief valve. 
 
Thermal expansion is the normal response of water when it is heated.  In a closed system, thermal expansion will cause 
the system pressure to build until the relief valve actuation pressure is equaled.  Then, the relief valve will open, allowing 
some water to escape, slightly lowering the pressure. 
 
Contact your water supplier or local plumbing inspector on how to control this situation. 
 
    
WARNING
 
Above all, do not plug the temperature and pressure relief valve.  This is not a solution and can create a hazardous 
situation. 
 
VENT AND AIR INTAKE SYSTEM 
Examine the vent and air intake system every 3 months.  Points of inspection are as follows: 
1.  Check for obstructions and/or deterioration of vent piping and vent terminal.  Replace immediately where needed. 
2.  Vent pipe and vent terminal screen should be cleaned of any foreign material.  The screen is located inside the vent 
terminal outlet and is accessible from the outside of the vent terminal elbow.  Do not reach inside the vent terminal 
when the water heater is in operation. 
3.  Check all venting system connections for leakage and reseal as required.  
 
COMBUSTION SYSTEM INSPECTION 
 
Inspect the operation of the combustion system monthly.  Use the following procedure to inspect the combustion system.  
1.  Turn off the main power switch of the water heater. 
2.  Adjust the thermostat to the Min. setting. 
3.  Remove the top of the combustion surround by unlatching it. 
4.  While observing the ignition module, turn on the main power switch. 
5.  Adjust thermostat to the Max. setting. 
6.  Watch the LED’s light as the controller goes through the S-OP as previously described. 
7.  Upon ignition, observe the main burner flame. 
8.  Readjust thermostat to previous setting. 
9.  Replace combustion surround top and latch it securely in place.