CONTROLS AND SWITCHES
This model is provided with three pressure switches. These switches 
are essential to the safe and proper operation of the unit. All switches 
are wired in series. The controller is set up to shut the unit down 
whenever there is a failure of any of the switches. It is important to 
understand the purpose of each switch. 
50 GALLON UNIT
75 GALLON UNIT
Figure: 2
BLOWER PROVER SWITCH
The  Blower  Prover  Switch  is  provided  on  the  heater  to  verify  that 
the fan is operating. It is a positive pressure switch whose electrical 
contacts are normally open. When the fan increases the pressure in 
the burner, the pressure switch will allow the electrical contacts to 
close. The pressure switch is connected to the blower pressure tap 
by a piece of tygon tubing. This tubing must be connected in order for 
the switch to change the electrical contacts. The controller requires 
that the electrical contacts on this air flow switch be open before it will 
allow the blower to come on.
BLOCKED EXHAUST SWITCH 
The Blocked Exhaust Switch is set up to shut the unit off when a build-
up of positive pressure in the exhaust vent pipe occurs. This switch 
is a positive pressure switch that requires an increase in pressure to 
change the electrical contacts from normally closed to open. When 
this switch prevents the unit from igniting, most likely the exhaust is 
blocked by some means. Check to see if the condensate is allowed 
to  flow  freely  from  the  exhaust  elbow  and  for  obstructions  in  the 
exhaust venting and exhaust vent terminal. Also verify that the vent 
length does not exceed the maximum allowed as shown in the Vent 
Section of this manual.
BLOCKED INTAKE SWITCH 
The Blocked Intake Switch is set up to shut the unit off when a 
build-up of negative pressure in the intake air pipe occurs. This 
switch is a negative pressure switch that requires an increase 
in  negative  pressure  to  change  the  electrical  contacts  from 
normally closed to open. The switch is connected to the pressure 
tap on the PVC pipe connected to the inlet of the blower. When 
this switch prevents the unit from igniting, most likely the intake 
is blocked. Verify that the screen on the intake air connection 
(conventional vent), the intake air pipe and termination (direct 
vent installations) are free of obstructions that may prevent air 
from entering the unit. Insure the screen on intake air connection 
has been removed on direct vent installations, see “Figure 13: 
AIR  INTAKE  SCREEN”. Also  verify  the  intake  air  pipe  length 
does  not  exceed  the  maximum  allowed  as  shown  in  the  Vent 
Section of this manual.
WATER HEATING ENABLE/DISABLE (ON/OFF) SWITCH
The Water Heating Enable/Disable (On/Off) Switch is a single-pole, 
single-throw rocker switch. This switch provides 24V power to the 
gas control valve. 
SPARK IGNITER
The Spark Igniter is a device that ignites the main burner by spark. 
When  high  voltage  is  applied  to  the  igniter,  spark  is  generated  to 
ignite the main burner.
Blocked 
Intake 
Switch
Blower 
Prover 
Switch
Blocked Exhaust 
Switch
Blower 
Prover 
Switch
Blocked 
Intake 
Switch