Change during operation: N = impossible, Y* = possible (enabled by using             ), Y= possible (enabled by using 
 
 ) 
 
 
-33- 
FUNC 
DATA
 
 
 
5    Selecting Function 
5-1 
 Function Selection List 
Table 5-1-1  Table of 
Function Selection List
 
 
 
Func-
tion 
code 
No
.
 
Name 
Setting range
 
Unit
 
Min. 
unit
 
Factory 
setting
 
Change 
during 
operation
 
User 
setting 
F00 
Data protection 
 
0: Data change enabled, 
1: Data protected
      
-
 
-
 
N
 
 
F01 
Frequency command 
0:Key operation (
,
key) 
1:Voltage input (terminal [12]) 
                (0 to +10Vdc, 0 to +5Vdc) 
2:Current input (terminal[C1]) 
                (4 to 20mAdc) 
3:Voltage input + current input 
           (terminals[12]+[C1]) 
4:Analog (VR built in drive) 
-
 
-
 
N
 
 
F02 
Operation method 
0: Keypad operation 
1: Terminal operation (STOP key active) 
2: Terminal operation (STOP key inactive) 
3: Terminal operation (STOP key active) 
with GE software 
4: Terminal operation (STOP key inactive) 
with GE software
 
-
 
-
 
N
 
 
F03 
Maximum output fre-
quency 
50 to 120Hz 
Hz 
60 
N
 
 
F04 
Base frequency 
25 to 120Hz 
Hz 
60 
N
 
 
F05 
F06 
Data cannot be changed. 
-
 
-
 
-
 
 
F07 
Acceleration time 
0.0 to 60.0s     
0.01 second is set when 0.0 is specified. 
0.1 
6.0 
 
F08 
Deceleration time 
0.1 to 60.0s 
0.1 
6.0 
 
F09 
Torque boost 
0,1 
Variable torque  
               characteristic
 
2 to 31:  Constant torque  
                   characteristic
 
-
 
13 
 
F:  Fundamental functions