Rack Mounting Guidelines
The DSR-6400 Series unit, with the supplied mounting brackets is designed for installation 
in an EIA standard 19-inch (480 mm) equipment rack. Place each unit in a stable and level 
position within the rack and ensure that all front enclosure screws are tightened to 14 in-
lbs. If multiple DSR-6400 Series units are installed in a rack assembly, the operator may 
choose to have a certification agency evaluate the condition of the rack. 
Mechanical Loading
The mounting rack location should be secure and level to avoid hazardous instability to the 
equipment due to uneven loading or weight distribution within the rack. 
Ambient Temperature
When installing a DSR-6400 Series unit within a closed or multi-unit rack, the ambient 
temperature may be greater than the ambient temperature within the room. Therefore, 
verify that the amount of air flow required for safe operation is not compromised 
(maximum temperature for the equipment is 40° C). Consideration should be given to the 
maximum rated ambient temperature for the unit’s location when planning for cooling and 
air circulation. To evacuate the unit’s warm air output from within the mounting rack, 
Motorola Mobility recommends the use of a fan on top of the rack. 
Circuit Overloading
If the unit is connected to a power strip, rather than a branch circuit’s direct connection, use 
special care to ensure that the unit is properly connected. Always consider the affect that 
overloading circuits might have on over-current protection and supply wiring. To ensure 
that circuits are not overloaded, read the DSR-6400 Series UL regulatory power label on 
top of the unit. Check all equipment power/amperage ratings to ensure the mounting rack 
power rating is not exceeded. 
Earth Ground
Reliable earthing of rack-mounted equipment should be maintained. Particular attention 
should be given to supply connections other than direct connections to the branch circuit (e.g. 
use of power strips). The RF-IN antenna cable should only be connected while the unit is 
properly grounded. The shield of the coaxial cable should be earthed in YP accordance with 
Article 820.93 of the NEC (National Electrical Code), ANSI/NFPA 70:2005, or equivalent. 
Battery Replacement
Do not replace the lithium battery used in the unit. Instead, return the unit to a Motorola 
Mobility authorized service center for replacement with the same or equivalent type 
battery as recommended by the manufacturer.