Cisco Systems 6807-XL Manual De Usuario

Descargar
Página de 118
Table 17: Power Requirements and Heat DissipationChassis and Fan Trays
Heat Diss.
(BTU/HR)
AC-Input Power
(Watts)
(Power-Allocated)
Module Power
(Watts)
(Power-Requested)
Module Current
(A) @ 52V
Model Number/
Module Type
887.15
260
260
5
C6807-XL-FAN
Table 18: Power Requirements and Heat DissipationSupervisor Engines
Heat Diss.
(BTU/HR)
AC-Input Power
(Watts)
(Power-Allocated)
Module Power
(Watts)
(Power-Requested)
Module Current
(A) @ 52V
Model Number/
Module Type
1206.53
353.60
353.60
6.80
VS-S2T-10G
1903.83
557.96
557.96
10.73
VS-S2T-10G-XL
Table 19: Power Requirements and Heat DissipationPolicy Feature Cards
Heat Diss.
(BTU/HR)
AC-Input Power
(Watts)
(Power-Allocated)
Module Power
(Watts)
(Power-Requested)
Module Current
(A) @ 52V
Model Number/
Module Type
507.45
130
130
2.5
VS-F6K-PFC4
507.45
148.72
148.72
2.86
VS-F6K-PFC4XL
Table 20: Power Requirements and Heat DissipationDistributed Forwarding Cards (DFCs)
Heat Diss.
(BTU/HR)
AC-Input Power
(Watts)
(Power-Allocated)
Module Power
(Watts)
(Power-Requested)
Module Current
(A) @ 52V
Model Number/
Module Type
422.28
123.76
123.76
2.38
WS-F6K-DFC4-E
Distributed
Forwarding Card E
486.16
142.48
142.48
2.74
WS-F6K-DFC4-EXL
Distributed
Forwarding Card
EXL
468.41
137.28
137.28
2.64
WS-F6K-DFC4-A
Distributed
Forwarding Card A
Cisco Catalyst 6807-XL Switch Hardware Installation Guide    
   OL-30656-01
75
Power Supply Specifications
Chassis and Module Power and Heat Values