CHAPTER 7:  Alarm Configuration
 
117
7.5. 
The Ping-No-Answer Alarm
The Ping-No-Answer Alarm is intended to provide notification when one of the IP 
addresses defined via the Ping-No-Answer Reboot feature (described in Section 6.1) 
fails to respond to a Ping command.  When one of the user-defined IP addresses fails 
to answer a Ping command, the Outlet Managed PDU can provide notification via 
Email, Syslog Message or SNMP Trap.
Notes:
•  In order for this alarm to function, IP Addresses for the Ping-
No-Answer reboot feature must first be defined as described in 
Section 6.1.
•  When a Ping-No-Answer condition is detected, the Outlet 
Managed PDU can still reboot the user-selected outlet(s) as 
described in Section 6.1, and can also send an email, Syslog 
Message and/or SNMP trap as described in this section.
•  In order for the Outlet Managed PDU to provide Email alarm 
notification, communication parameters must first be defined as 
described in Section 5.9.11.
•  In order for the Outlet Managed PDU to provide Syslog Message 
notification, Syslog parameters must first be defined and Syslog 
Messages must be enabled as described in Section 5.9.2 and 
Section 11.
•  In order for the Outlet Managed PDU to provide SNMP Trap 
notification when this alarm is triggered, SNMP parameters must 
first be defined, and SNMP Traps must be enabled as described 
in Section 5.9.7 and Section 12.
To configure the Ping-No-Answer Alarm, you must access the Outlet Managed PDU 
command mode using a password that permits Administrator Level commands.  The 
Ping-No-Answer alarm configuration menu offers the following parameters:
•  Trigger Enable:  Enables/Disables the trigger for this alarm.  When 
Disabled, this alarm will be suppressed.  (Default = On.)
Note:
To cancel an alarm without correcting the condition that caused the 
alarm, simply toggle the Trigger Enable parameter to Off and then 
back On again.
•  Resend Delay:  Determines how long the Outlet Managed PDU will wait to 
resend an email message generated by this alarm, when the initial attempt to 
send the notification was unsuccessful.  (Default = 60 Minutes.)