Black Box MPSH16-D20-120V Manual De Usuario

Descargar
Página de 193
OUTLET MANAGED PDU
 
132
8.6. 
The Current History Screen
The Current History Screen displays current, voltage and temperature readings as a 
function of time.  In the Web Browser Interface, the Current History can be displayed 
as a graph or downloaded in ASCII, CSV or XML format.  In the Text Interface, 
the Current History can be displayed as straight ASCII data, or can be downloaded 
in CSV or XML format.  To view the Current History Screen, access the Outlet 
Managed PDU command mode, and proceed as follows:
Text Interface:  Type 
/L and press [Enter] to access the "Display Logs" main 
menu.  From the "Display Logs" menu, type 
3 and press [Enter] to display the 
Current Metering Log Menu.  From the Current Metering Log Menu, you can 
display current history data in ASCII, CSV or XML format or erase the existing 
Current Metering Log.  The Text Interface also allows you to select the following 
display parameters:
•  Display Data Option:  Determines whether data will be displayed in "Unit" 
format (displays total current per branch) or "Plug" format (displays current 
consumption for each individual outlet.)
Web Browser Interface:  Place the cursor over the "Current Metering" link on the 
left hand side of the screen.  When the fly-out menu appears, click on the "Current 
History" link to display the Current Metering Log menu.  At the Current Metering 
Log menu, you can display current history data as a graph, or download or display 
the log in ASCII, CSV or XML format.  The Web Browser Interface also allows you 
to select the following display parameters:
•  Select Plugs:  Determines whether the Outlet Managed PDU will display 
total current for all outlets, total current for one or more Plug Groups or total 
current for up to four individual. user-selected outlets.
•  Plug Groups:  Determines which user-defined plug groups will be included 
in the Current History Data.
•  Plugs:  Determines which plugs will be included in the Current History Data.
•  Date Range:  Determines whether the Outlet Managed PDU will display 
current consumption data for the previous Day, Week, Month or Year.  Also 
allows "Live" data display, which shows current consumption for the past ten 
minutes (approximately.)