QT027
kW RATING 
27
ENGINE SIZE 
2.4 Liter Inline 4
GENERATOR OUTPUT VOLTAGE/KW - 60Hz 
KW Nat. Gas  AMP 
KW LPG 
AMP  CB Size (Both)
 120/208V, 3-phase, 0.8 pf
25
87
27
94
100
GENERATOR LOCKED ROTOR KVA
 AVAILABLE @ VOLTAGE DIP OF 35%
 Single phase or 208 3-phase
43
ENGINE FUEL CONSUMPTION 
(Natural Gas) (Propane)
  
Natural Gas (25 kW)
Propane (27 kW)
   
 
 (ft
3
/hr.)
(gal/hr.)
cu ft/hr
 Exercise cycle
42
0.44
16
 25% of rated load
108
1.2
44
 50% of rated load
197
2.2
81
 75% of rated load
287
3.2
118
 100% of rated load
359
4.1
147
ENGINE COOLING
  
Air flow
(inlet air including alternator and combustion air) 
ft
3
/min.
2,400
 System coolant capacity
US gal.
2.5
 Heat rejection to coolant
BTU/hr.
120,000
 Max. operating air temp. on radiator
°C (°F)
60 (150)
 Max. ambient temperature
°C (°F)
50 (140)
COMBUSTION AIR REQUIREMENTS
  
Flow at rated power 60 Hz
cfm
68
SOUND EMISSIONS IN DBA
 Exercising at 7 meters
61
 Normal operation at 7 meters
70
EXHAUST
 Exhaust flow at rated output 60 Hz
cfm
130
 Exhaust temp. at muffler outlet
°F
900
ENGINE PARAMETERS
  
Rated synchronous RPM
60 Hz
1800
 HP at rated KW
60 Hz
40
POWER ADJUSTMENT FOR AMBIENT CONDITIONS
 Temperature Deration
 
3% for every 10 °C above - °C
25
 
1.65% for every 10 °F above - °F
77
 Altitude Deration
 
1% for every 100 m above - m
183
 
3% for every 1000 ft. above - ft.
600
ENCLOSURE
  
Material
Aluminum
  Color
PMS 422 (Bisque)
OPERATING DATA
QT027
RATING:   All three phases units are rated at 0.8 power factor. All single phase units are rated at 1.0 power factor. STANDBY RATING: Standby ratings
apply to installations served by a reliable utility source. The standby rating is applicable to varying loads for the duration of a power outage. There is
no overload capability for this rating. Ratings are in accordance with ISO-3046-1. Design and specifications are subject to change without notice.