section 3
DescRiption & coMponents
2
162
Figure 3-5. – Excitation Circuit Breaker
VOLTAGE REGULATOR:
A  typical Voltage  Regulator  is  shown  in  Figure  3-6 
(12.5 & 15 kW Units) or Figure 3-7 (17.5 kW Units). 
Unregulated  AC  output  from  the  stator  excitation 
winding  is  delivered  to  the  regulator’s  DPE  termi-
nals, via Wire 2, the Excitation Circuit Breaker and 
Wire 162, and Wire 6. The Voltage Regulator recti-
fies  that  current  and,  based  on  stator  AC  power 
winding  sensing,  regulates  it.  The  rectified  and 
regulated excitation current is then delivered to the 
rotor windings from the positive (+) and negative (-) 
regulator  terminals,  via  Wire  4  and  Wire  0.  Stator 
AC power winding “sensing” is delivered to the reg-
ulator “SEN” terminals via Wires 11S and 44S.
The  regulator  provides “over-voltage”  protection,  but 
does  not  protect  against  “under-voltage”.  On  occur-
rence of an “over-voltage” condition, the regulator will 
“shut  down”  and  complete  loss  of  excitation  current 
to  the  rotor  will  occur. Without  excitation  current,  the 
generator AC output voltage will drop to approximately 
one-half (or lower) of the unit’s rated voltage.
Figure 3-6. – Typical Voltage Regulator Found on 12.5 
kW and 15 kW Units
Figure 3-7. – Typical Voltage Regulator Found on 17.5 
Units
ADJUSTMENT PROCEDURE (12.5 AND 15 KW UNITS):
The Voltage  Regulator  is  equipped  with  three  light 
emitting  diodes  (LED’s). These  LED’s  are  normally 
on  during  operation  with  no  faults  in  the  system The 
RED  regulator  LED  is  on  when  the  regulator  is  on 
and  functioning. The Yellow  sensing  LED  is  powered 
by  sensing  input  to  the  regulator  from  the  stator  AC 
power windings. The GREEN excitation LED  is pow-
ered by stator excitation winding output.
Four  adjustment  potentiometers  are  provided. They 
are  VOLTAGE  ADJUST,  GAIN,  STABILITY,  and 
UNDERFREQUENCY ADJUST.
1. Connect an AC Voltage/Frequency meter across wires 11 & 44
at  the  50A  Main  circuit    breaker. Verify  frequency  is  between
59-61Hz.
2. On the regulator, set the adjustment pots as follows.
a. Voltage Adjust – Pot-turn fully counterclockwise
b. Gain – turn to midpoint (12 O’clock)
c. Stability – turn to midpoint (12 O’clock)
d. Under Frequency – turn to midpoint (12 O’clock)
3. Start the generator. This adjustment will be done under a no-
load condition.
4. Turn the regulator’s Voltage Adjust pot clockwise to obtain a line
to line voltage of 238-242 VAC.
5. If the red regulator LED is flashing, slowly turn the stability pot
either direction until flashing stops.
ADJUSTMENT PROCEDURE (17.5 KW UNITS):
A single red lamp (LED) glows during normal opera-
tion. The  lamp  will  become  dim  if  excitation  winding 
AC output diminishes. It will go out on occurrence of 
an open condition in the sensing AC output circuit.
An  adjustment  potentiometer  permits  the  stator  AC 
power  winding  voltage  to  be  adjusted.  Perform  this 
adjustment with the generator running at no-load, and 