KW RATING 
60
ENGINE SIZE 
2.4 Liter
GENERATOR OUTPUT VOLTAGE/KW - 60Hz 
KW 
AMP 
CB Size
 120/240V, 1-phase, 1.0 pf
60
250
300
GENERATOR LOCKED ROTOR KVA
 AVAILABLE @ VOLTAGE DIP OF 35%
 Single phase or 208/240 3-phase
120
ENGINE FUEL CONSUMPTION 
(Natural Gas) (Propane)
  
Natural Gas
Propane
   
 
 (ft
3
/hr.)
(gal/hr.)
cu ft/hr
 Exercise cycle
123
1.34
49.3
 25% of rated load
267
2.7
101
 50% of rated load
483
5.0
183
 75% of rated load
672
7.0
255
 100% of rated load
862
9.0
327
ENGINE COOLING
  
Air flow
(inlet air including alternator and combustion air) 
ft
3
/min.
3,280
 System coolant capacity
US gal.
2.5
 Heat rejection to coolant
BTU/hr.
270,000
 Max. operating air temp. on radiator
°C (°F)
60 (150)
 Max. ambient temperature
°C (°F)
50 (140)
COMBUSTION AIR REQUIREMENTS
  
Flow at rated power 60 Hz
cfm
180
SOUND EMISSIONS IN DBA
 Exercising at 7 meters
65
 Normal operation at 7 meters
72
EXHAUST
 Exhaust flow at rated output 60 Hz
cfm
494
 Exhaust temp. at muffler outlet
°F
1,050
ENGINE PARAMETERS
  
Rated synchronous RPM
60 Hz
3600
 HP at rated KW
60 Hz
94
POWER ADJUSTMENT FOR AMBIENT CONDITIONS
 Temperature Deration
 
3% for every 10 °C above - °C
25
 
1.65% for every 10 °F above - °F
77
 Altitude Deration
 
1% for every 100 m above - m
915
 
3% for every 1000 ft. above - ft.
3000
OPERATING DATA
60 kW
RATING: All three phases units are rated at 0.8 power factor. All single phase units are rated at 1.0 power factor. STANDBY RATING: Standby ratings
apply to installations served by a reliable utility source. The standby rating is applicable to varying loads for the duration of a power outage. There is
no overload capability for this rating. Ratings are in accordance with ISO-3046-1. Design and specifications are subject to change without notice.