COMMERCIAL 80 kW 
KW RATING 
80
ENGINE SIZE 
4.6 Liter V-8
GENERATOR OUTPUT VOLTAGE/KW - 60Hz 
KW 
AMP 
CB Size
  120/240V, single phase, 1.0 pf 
80 LP / 78 NG 
333.3 LP / 325 NG 
400
  120/208V, 3-phase, 0.8 pf 
80 LP / 78 NG 
277.9 LP / 270.9 NG 
300
  120/240V, 3-phase, 0.8 pf 
80 LP / 78 NG 
240.8 LP / 234.8 NG 
300
  277/480V, 3-phase, 0.8 pf 
80 LP / 78 NG 
120.4 LP / 117.4 NG 
150
GENERATOR LOCKED ROTOR KVA
 AVAILABLE @ VOLTAGE DIP OF 35%
  Single phase or 208V & 240V 3-phase 
 
160
 480V 
3-phase 
 
185
   
 
 
ENGINE FUEL CONSUMPTION 
(Natural Gas) (Propane)
 
 
Natural Gas 
Propane  
  
 
 
(ft3/hr.) (gal/hr.) 
cu 
ft/hr
 Exercise 
cycle 
 
131 
1.45 
53 
  25% of rated load 
 
312 
3.45 
126
  50% of rated load 
 
600 
6.64 
241 
 
  75% of rated load 
 
835 
9.25 
336
  100% of rated load 
 
1154 
12.78 
465
   
ENGINE COOLING
 Air 
flow 
(inlet air including alternator and combustion air)
 ft3/min. 5,300
  System coolant capacity 
US gal. 
 4.0
  Heat rejection to coolant 
 BTU/hr. 
316,000
  Max. operating air temp. on radiator 
°C (°F) 
60 (150)
  Max. ambient temperature 
°C (°F) 
50 (140)
COMBUSTION AIR REQUIREMENTS
  Flow at rated power 60 Hz 
cfm 
250
   
SOUND EMISSIONS IN DBA
  db(A) @ 23 feet in exercise mode 
 
64 
  db(A) @ 23 feet at normal operating load 
 
74 
 
EXHAUST
  Exhaust flow at rated output 60 Hz 
m3/min. (cfm) 
720 
  Exhaust temp. at muffler outlet 
°F 
840 
ENGINE PARAMETERS
  Rated synchronous RPM 
60 Hz 
3600
  HP at rated KW 
60 Hz 
130
POWER ADJUSTMENT FOR AMBIENT CONDITIONS
 Temperature 
Deration
   
3% for every 10 °C above - °C 
25 
   
1.65% for every 10 °F above - °F 
77
 Altitude 
Deration 
   
1% for every 100 m above - m 
183 
 
   
3% for every 1000 ft. above - ft. 
600
OPERATING DATA
COMMERCIAL 80 kW
RATING: All three phases units are rated at 0.8 power factor. All single phase units are rated at 1.0 power factor. STANDBY RATING: Standby ratings apply to installations served by a reliable utility 
source. The standby rating is applicable to varying loads for the duration of a power outage. There is no overload capability for this rating. Ratings are in accordance with ISO-3046-1. Design and 
specifications are subject to change without notice. Maximum wattage and current are subject to and limited by such factors as fuel Btu content, ambient temperature, altitude, engine power 
and condition, etc.
COMMERCIAL SERIES