1.  Turn off utility power to the main distribution 
panel in the house. This can be done by switching 
the service main breaker to the off or open posi-
tion.
2.  Allow the generator to start. Before loading the 
generator, confirm that the No Load Frequency, 
with the roof open and door off, is set to 63-63.5 
Hz. Transfer load to emergency circuits.
3.  Turn on appliances, lights, pumps, etc., that are 
on the emergency circuits in an attempt to fully 
load the generator. Be cautious not to overload 
the generator. Use the following chart as a guide:
4.  When 3/4 load has been achieved. Connect a fre-
quency meter to the output lugs of the generator’s 
main line circuit breaker.
5.  The fuel regulator is fitted with one adjustment 
screw. While watching the frequency meter, slowly 
turn the adjustment screw clockwise or counter-
clockwise until the highest frequency is read on 
the meter. Only limited adjustment is available 
because of the set pin. Under no circumstances 
should any of the pins be removed (Figure 2.1).
 Figure 2.1 — 7kW Fuel Regulator
410cc Engine
Adjustment
Screw
(One Side
Only)
Set
Pin
6.  When the highest frequency is reached maximum 
power has been set. From this point turn the 
adjustment screw 1/4 turn counterclockwise. The 
regulator is now set.
7.  Turn utility power to the main distribution panel 
back on. This can be done by switching the ser-
vice main breaker to the on or closed position. 
Allow the generator to shut down.
  Do not make any unnecessary adjustments. 
Factory settings are correct for most applica-
tions. However, when making adjustments, be 
careful to avoid overspeeding the engine.
If this procedure or the test equipment is not avail-
able, locate the nearest Dealer and they can perform 
the adjustments.
NOTE:
A service fee may be charged for this adjustment.
2.7  ENGINE GOVERNOR ADJUSTMENT
If both AC frequency and voltage are correspondingly 
high or low, adjust the engine governor as follows:
2.7.1  7 KW UNITS
  The engine must be OFF to perform steps 1 and 
2.
1.  Loosen the governor clamp bolt (Figures 2.2).
2.  Hold the governor lever at its wide open throttle 
position (clockwise), and rotate the governor 
shaft clockwise as far as it will go. Then, tighten 
the governor lever clamp bolt to 70 inch-pounds 
(8 N-m).
3.  Start the generator; let it stabilize and warm up 
at no-load.
Figure 2.2 — Engine Governor Adjustment 
Single Cylinder Engines
GOVERNOR
SHAFT
PRIMARY
ADJUST
SCREW
GOVERNOR
CLAMP
BOLT
SECONDARY
ADJUST SCREW
‹
 
Unit 
120 Volts 
240 Volts
 
7 kW 
50.0 amps 
25.0 amps
Section 2 — Post Installation Start-up and Adjustments
Air-cooled Generators