Guardian Technologies 04760-2 Manual De Usuario

Descargar
Página de 56
DANGER
  Only qualified electricians or contractors should 
attempt such installations, which must comply 
strictly with applicable codes, standards and 
regulations.
1.1 UNPACKING/INSPECTION
After unpacking, carefully inspect the contents for 
damage. 
• This standby generator set has been factory sup-
plied with a weather protective enclosure that is 
intended for outdoor installation only.
  If this generator is used to power electrical load 
circuits normally powered by a utility power 
source, it is required by code to install a trans-
fer switch. The transfer switch must effectively 
isolate the electrical system from the utility 
distribution system when the generator is oper-
ating (NEC 700, 701 and 702). Failure to isolate 
an electrical system by such means will result in 
damage to the generator and also may result in 
injury or death to utility power workers due to 
backfeed of electrical energy.
If any loss or damage is noted at time of delivery, have 
the person(s) making the delivery note all damage on 
the freight bill or affix his or her signature under the 
consignor's memo of loss or damage.
If a loss or damage is noted after delivery, separate 
the damaged materials and contact the carrier for 
claim procedures.
“Concealed damage” is understood to mean damage 
to the contents of a package that is not in evidence at 
the time of delivery, but is discovered later.
1.2 PROTECTION 
SYSTEMS
Unlike an automobile engine, the generator may have 
to run for long periods of time with no operator pres-
ent to monitor engine conditions. For that reason, the 
engine is equipped with the following systems that 
protect it against potentially damaging conditions:
1.  Low Oil Pressure Sensor 
3.  Overcrank
2. High 
Temperature 
Sensor 
4. Overspeed
There are LED readouts on the control panel to indi-
cate that one of these faults has occurred. There is 
also a “System Set” LED that is described below.
1.3  SYSTEM SET LED
The “System Set” LED is lit when all of the following 
conditions are true:
1.  The AUTO/OFF/MANUAL switch is set to the 
AUTO position.
2.  The utility voltage being supplied to the unit is 
being sensed by the Control PCB. If the utility 
sense voltage is not connected to the unit or if it 
is below 168 volts AC, then the system set light 
will flash rapidly. This indicates that if the AUTO/
OFF/MANUAL switch is placed in the Auto posi-
tion , the generator will start.
3.  The “Not In Auto” dip switch is set to the OFF 
position on the control board.
4.  No alarms are present, for example, low oil pres-
sure, high temperature, etc.
Section 1 — General Information
Air-cooled 7 kW, 12 kW and 15 kW Generators
 4