1.9  
RECONFIGURING THE
FUEL SYSTEM
1.9.1  7 KW, 410CC ENGINE
To reconfigure the fuel system from NG to LP, follow 
these steps (Figure 1.4):
NOTE:
The primary regulator for the propane supply is 
NOT INCLUDED with the generator. A fuel pres-
sure of 10 to 12 inches of water column (0.36 to 
0.43 psi) to the fuel inlet of the generator MUST 
BE SUPPLIED.
1.  Turn off the main gas supply (if connected).
2.  Open the roof and remove the door.
3.  Remove the battery (if installed).
4.  Disconnect wire #0 and wire #14 from the gas 
solenoid on top of the demand regulator.
5.  Remove the carburetor fuel hose from the outlet 
port of the demand regulator.
6.  Remove the demand regulator by removing the 
fastener that retains the regulator mounting 
bracket.
7.  Remove the square headed steel pipe plug from 
outlet port #1 and the brass hose barb fitting 
from outlet port #2.
8.  Refit the brass hose barb fitting to outlet port #1 
and the square headed steel pipe plug to outlet 
port #2.
 Figure 1.4 – Demand Regulator
NG FUEL SYSTEM
LP FUEL SYSTEM
FUEL HOSE
BRASS HOSE 
FITTING
BRASS HOSE 
FITTING
FUEL JET
OUTLET
PORT
FUEL HOSE
ADJUSTMENT
SCREW
HOSE & PLUG
SWITCHED SIDES
PIPE
PLUG
STATIC 
PRESSURE 
TAP
RUNNING 
PRESSURE 
TAP
‹
NOTE:
Use an approved pipe sealant or joint compound 
on all threaded fittings to reduce the possibility 
of leakage.
9.  Reverse procedure steps 1-6 to reinstall demand 
regulator.
10. Take the plastic plug supplied in the poly-bag 
with the generator and press it into the 3/4” hole 
on the bottom of the air cleaner base (Figure 
4.6).
11. Reverse the procedure to convert back to natural 
gas.
12. Check for gas leakage at the pipe plug, hose con-
nection and fittings.
1.9.2  10, 13 AND 16KW, V-TWIN ENGINES
To reconfigure the fuel system from NG to LP, follow 
these steps:
NOTE:
The primary regulator for the propane supply is 
NOT INCLUDED with the generator. A fuel pres-
sure of 10 to 12 inches of water column (0.36 to 
0.43 psi) to the fuel inlet of the generator MUST 
BE SUPPLIED.
1. Open 
the 
roof.
2.  For 10kW units:  Loosen clamp and slide back 
the air inlet hose.
• Slide fuel selector on carburetor out towards the 
back of the enclosure (Figures 1.5 and 1.6).
• Return the inlet hose and tighten clamp secure-
ly.
 
For 13 and 16kW units: remove the air cleaner 
cover.
• Slide the selector lever out towards the back of 
the enclosure (Figures 1.7 and 1.8).
• Return the air cleaner cover and tighten the two 
thumb screws.
3. Close 
the 
roof.
4.  Reverse the procedure to convert back to natural 
gas.
‹
Section 1 — General Information
Air-cooled Generators
 8