 3.9   BATTERY MAINTENANCE
All lead-acid batteries will discharge when not in 
use. The generator battery should be inspected as 
follows:
3.9.1 WEEKLY
 
‹
Inspect the battery posts and cables for tightness 
• 
and corrosion. Tighten and clean as necessary.
Check the battery fluid level of unsealed batteries 
• 
and, if necessary, fill with Distilled Water Only. Do 
not use tap water in batteries.
3.9.2  EVERY SIX MONTHS
 
‹
Have the state of charge and condition checked. 
• 
This should be done with an automotive-type bat-
tery hydrometer. 
NOTE:
Servicing of the battery is to be performed or 
supervised by personnel knowledgeable of batter-
ies and the required precautions. Keep unauthor-
ized personnel away from batteries.
Damage will result if the battery connections are 
made in reverse.
DANGER
  Do not dispose of the battery in a fire. The 
battery is capable of exploding. Storage batter-
ies give off explosive hydrogen gas. This gas can 
form an explosive mixture around the battery 
for several hours after charging. The slightest 
spark can ignite the gas and cause an explo-
sion. Such an explosion can shatter the battery 
and cause blindness or other injury. Any area 
that houses a storage battery must be properly 
ventilated. Do not allow smoking, open flame, 
sparks, or any spark producing tools or equip-
ment near the battery. Discharge static electric-
ity from body before touching the battery by 
first touching a grounded metal surface.
  A battery presents a risk of electrical shock 
and high short circuit current. The following pre-
cautions are to be observed when working on 
batteries:
• Remove watches, rings or other metal objects;
• Use tools with insulated handles;
• Wear rubber gloves and boots;
•  Do not lay tools or metal parts on top of the 
battery;
•  Disconnect any charging source prior to connecting 
or disconnecting battery terminals; and
•  Do not use any jumper cables or booster battery to 
crank and start the generator engine. If any battery 
has discharged, remove it for recharging.
  Do not open or mutilate the battery. Released 
electrolyte has been known to be harmful to the 
skin and eyes, and to be toxic.
  The electrolyte is a dilute sulfuric acid that is 
harmful to the skin and eyes. It is electrically 
conductive and corrosive. The following 
procedures are to be observed:
• Wear full eye protection and protective clothing;
•  Where electrolyte contacts the skin, wash it off 
immediately with water;
•  Where electrolyte contacts the eyes, flush 
thoroughly and immediately with water and seek 
medical attention; and
•  Spilled electrolyte is to be washed down with an 
acid neutralizing agent. A common practice is to 
use a solution of 1 pound (500 grams) bicarbonate 
of soda to 1 gallon (4 liters) or water. The bicar-
bonate of soda solution is to be added until the 
evidence of reaction (foaming) has ceased. The 
resulting liquid is to be flushed with water and the 
area dried.
 3.10  MAJOR SERVICE MANUAL
To obtain a service manual for the generator, contact 
the nearest Authorized Service Dealer. Make sure to 
identify the MODEL NUMBER and SERIES.
 3.11  EXERCISING THE GENERATOR
The manufacturer recommends that the generator be 
started and operated at least once every seven days. 
Let the unit run for at least 30 minutes to “exercise” 
the engine.
 3.12  OUT OF SERVICE PROCEDURE
3.12.1  REMOVAL FROM SERVICE
 
‹
If the generator cannot be exercised every seven days, 
and it is to be out of service longer than 30 days, pre-
pare the generator for storage as follows:
1.  Start the engine and let it warm up.
2.  Close the fuel shutoff valve in the fuel supply line 
and allow the unit to shut down.
Note:
Using a fuel additive such as STA-BIL fuel stabi-
lizer, or an equivalent, will prevent gum deposits 
from forming in the engine’s fuel system.
3.  While the engine is still warm from running, drain 
the oil completely. Refill the crankcase with SAE 
10W-30 oil having API classification “For Service 
SF.”
Section 3 – Maintenance
Recreational Vehicle Generator