•  Intake — 0.15 ± 0.02mm (cold), (0.006" ± 0.0008" inches)
•  Exhaust — 0.20 ± 0.02mm (cold) (0.008" ± 0.0008" inches)
After the first 50 hours of operation, check the valve clearance 
in the engine and adjust if necessary.
Important: 
If feeling uncomfortable about doing this procedure or 
the proper tools are not available, please take the generator to the 
nearest service center to have the valve clearance adjusted. This is 
a very important step to ensure longest life for the engine.
The generator should be started at least once every thirty days and 
be allowed to run at least 30 minutes. If this cannot be done and 
the unit must be stored for more than 30 days, use the following 
information as a guide to prepare it for storage.
NEVER store engine with fuel in tank indoors 
or in enclosed, poorly ventilated areas where 
fumes may reach an open flame, spark or pilot 
light as on a furnace, water heater, clothes dryer 
or other gas appliance.
Allow unit to cool entirely before storage.
It is important to prevent gum deposits from forming in essential 
fuel system parts such as the carburetor, fuel hose or tank during 
storage. Also, experience indicates that alcohol-blended fuels 
(called gasohol, ethanol or methanol) can attract moisture, which 
leads to separation and formation of acids during storage. Acidic 
gas can damage the fuel system of an engine while in storage.
To avoid engine problems, the fuel system should be emptied 
before storage of 30 days or longer, as follows:
•  A quality fuel stabilizer should be added to the existing fuel per 
the manufacturers specifications.
Drain fuel into approved container outdoors, 
away from open flame. Be sure engine is cool. 
Do not smoke.
•  Start and run the engine for 10 - 15 minutes, after that time and 
while the unit is running, turn the fuel shut-off valve OFF and run 
until the engine stops from lack of fuel.
•  Allow the engine to cool, then remove all gasoline from the fuel 
tank. Use a commercially available, non-conductive vacuum 
siphon. Drain oil from crankcase. Refill the crankcase with 
recommended grade oil.
•  Remove spark plug and spray with a quality fogging agent, or 
pour about 1/2 ounce (15 ml) of engine oil into the cylinder. 
Cover spark plug hole with rag. Pull the recoil starter a couple 
times to lubricate the piston rings and cylinder bore.
Avoid spray from spark plug hole when 
cranking engine.
•  Install and tighten spark plug. Do not connect spark plug wire.
• Clean the generator's outer surfaces. Check that cooling air 
slots and openings on generator are open and unobstructed.
•  Store the unit in a clean, dry place.
•  Do not store gasoline from one season to another.
•  Replace the gasoline can if it starts to rust. Rust and/or dirt in 
the gasoline will cause problems with the carburetor and fuel 
system.
•  If possible, store the unit indoors and cover it to give protection 
from dust and dirt. BE SURE TO EMPTY THE FUEL TANK.
• If it is not practical to empty the fuel tank and the unit is to 
be stored for some time, use a commercially available fuel 
stabilizer  added  to  the  gasoline  to  increase  the  life  of  the 
gasoline. Start and run the engine for 10 - 15 minutes, after that 
time and while the unit is running, turn the fuel shut-off valve 
OFF and run until the engine stops from lack of fuel.
• Cover the unit with a suitable protective cover that does not 
retain moisture.
NEVER cover the generator while engine and 
exhaust area are warm.
  
15
Maintenance