LIQUID FLOW SWITCHES
SPECIFICATION DATA & MOUNTING INSTRUCTIONS
S6065A1003
S6065A2001
GENERAL
The S6065A1003 and S6065A2001 Liquid Flow Switches are
designed for monitoring flow rates in pipes employed in HVAC
applications. They are suitable for monitoring flow in water,
oil, cooling circuits, and lubrication systems. The S6065A2001
is designed for monitoring aggressive liquids.
See Table 1 for the reset and switch points for water. Data for
other media must be determined empirically.
designed for monitoring flow rates in pipes employed in HVAC
applications. They are suitable for monitoring flow in water,
oil, cooling circuits, and lubrication systems. The S6065A2001
is designed for monitoring aggressive liquids.
See Table 1 for the reset and switch points for water. Data for
other media must be determined empirically.
FEATURES
•
Cost-effective flow switches for HVAC applications.
• High-capacity,
fully-encapsulated NC/NO micro-switch.
•
A single type suitable for pipes with a diameter of 1 to 8".
COMMON SPECIFICATIONS
Switching capacity
15 (8) A, 24...250 Vac
Lifetime
50000 cycles at nominal load
Working temperature
-40...+85 °C at 90% rel. humidity,
non-condensing
non-condensing
Electrical connection
Screw terminal, wire up to 1.5 mm
2
cable
∅ 6...9
mm
Protection class
I according to EN60730
Protection standard
IP65 according to EN60529
Housing material
ABS and corrosion-protected steel
Accessories
PA2 Paddle set
MOUNTING
The S6065A1003 and S6065A2001 Liquid Flow Switches can
be mounted in any desired position far from elbows, valves,
and filters.
NOTE: The arrow on the housing must point downstream.
be mounted in any desired position far from elbows, valves,
and filters.
NOTE: The arrow on the housing must point downstream.
When using multiple paddles, the paddles must be
arranged in order of decreasing length downstream,
i.e. with the longest paddle facing the oncoming
liquid.
arranged in order of decreasing length downstream,
i.e. with the longest paddle facing the oncoming
liquid.
In the case of vertical pipes, reset the range to balance the
paddle weight. To prevent malfunction caused by impurities in
the medium, do not mount the device with the housing
pointing downwards.
paddle weight. To prevent malfunction caused by impurities in
the medium, do not mount the device with the housing
pointing downwards.
MODELS
Specification
S6065A1003
S6065A2001
Flow medium
non-aggressive liquid
aggressive liquid
Mounting
Rp 1" (ISO7/1)
Rp 1" (ISO7/1)
Maximum pipe temperature
120 °C
120 °C
Pressure
11 bar
30 bar
Paddle material
1.4401
1.4401
Lever yellow
brass
1.4404
Sensor body
yellow brass
1.4404
Housing dimensions
113 x 70 x 65 mm
108 x 70 x 72 mm
Weight
850 g
850 g
Approvals TÜV-approved
TÜV-approved