DCA-125USJ (50 HZ) — OPERATION AND PARTS MANUAL — REV. #0  (03/11/05) — PAGE 41
1
DCA-125USJ (50 HZ)— GENERATOR START-UP PROCEDURE (AUTO MODE)
1. Perform steps 1 through 5 in the 
Before Starting  section
as outlined in the 
Manual Starting Procedure.
3. Continue to follow the steps outlined in the 
Manual Start-
up procedure (start at step 9).
When running the generator in the AUTO
mode, remember the generator can start
up at any time without warning. NEVER
attempt to perform any maintenance when
the generator is in the auto mode.
WARNING:
When connecting the generator to a
isolation (transfer) switch, ALWAYS have
power applied to the generator's internal
battery charger. This will ensure that the
engine will not fail due to a dead battery.
CAUTION:
Figure 54.  MPEC Control Switch (AUTO)
2. Place the 
MPEC Control Switch (Figure 54) in the
AUTO position .
When the generator is set in the
AUTO mode, the generator will
automically start in the event
of comercial power falling below
a prescribed level by means of
a contact closure that is
generated automatically by a
transfer switch.
NOTE
Starting (Auto Mode)
DANGER:
Before connecting this
generator to any
building’s electrical
system, a 
licensed
electrician must install an isolation (transfer)  switch.
Serious damage to the building’s electrical system may occur
without this transfer switch.