GENERATOR AC LEAD CONNECTIONS
See “Voltage Codes”. This generator may be rated
at any one of three voltages, either single-phase or
three-phase. The electrical wires in the unit’s AC con-
nection (lower) panel should be installed according to
the number of leads and the voltage/phase required
for the application. If there are any questions regard-
ing lead connection, refer to the wiring diagrams at
the back of this manual.
at any one of three voltages, either single-phase or
three-phase. The electrical wires in the unit’s AC con-
nection (lower) panel should be installed according to
the number of leads and the voltage/phase required
for the application. If there are any questions regard-
ing lead connection, refer to the wiring diagrams at
the back of this manual.
Voltage codes apply to the type of stator assembly
installed on a particular generator.
installed on a particular generator.
FOUR-LEAD, SINGLE-PHASE STATOR
Four-lead generators (see Figure 7.1) are designed to
supply electrical loads with voltage code “A” (240V,
1-phase, 60 Hz). Electrical power is produced in the
stator power windings. These windings were con-
nected at the factory to the main circuit breaker as
shown in Figure 7.1.
supply electrical loads with voltage code “A” (240V,
1-phase, 60 Hz). Electrical power is produced in the
stator power windings. These windings were con-
nected at the factory to the main circuit breaker as
shown in Figure 7.1.
The rated voltage between each circuit breaker ter-
minal is 240V. The rated voltage between each circuit
breaker terminal and the neutral point 00 is 120V.
minal is 240V. The rated voltage between each circuit
breaker terminal and the neutral point 00 is 120V.
Figure 7.1 — Four-lead, Single-phase Stator
ALTERNATOR POWER WINDING
CONNECTIONS
CONNECTIONS
3-PHASE ALTERNATORS
The generator is designed to supply 3-phase electri-
cal loads. Electric power is produced in the alterna-
tor power windings. These windings were connected
at the factory to the main circuit breaker with a “Y”
configuration as shown in Figures 7.2 and 7.3.
cal loads. Electric power is produced in the alterna-
tor power windings. These windings were connected
at the factory to the main circuit breaker with a “Y”
configuration as shown in Figures 7.2 and 7.3.
The rated voltage between circuit breaker terminals
E1-E2, E1-E3 and E2-E3 is either 480V or 208V
depending on the model.
E1-E2, E1-E3 and E2-E3 is either 480V or 208V
depending on the model.
The rated voltage between each circuit breaker termi-
nal and the neutral point 00 is either 277V or 120V
depending on the model.
nal and the neutral point 00 is either 277V or 120V
depending on the model.
Figure 7.2 — Stator Power Winding
Connections - 3-phase, 277/480V (6 Lead)
S6
E3 S3
INTERNAL
CONNECTIONS
L-N
L-L
S4
E2
S2
S5
S1 E1
NEUTRAL
Figure 7.3 — Stator Power Winding
Connections - 3-phase, 120/208V (6 Lead)
E3
E2
00 (NEUTRAL)
E1
L-L
L-N
S1
S1
S4
S4
S6
S6
S3
S3
S5
S5
S2
S2
7-1
Standby Generator Sets
General Information
ACConn001 Re
v. 0 08/05