Siemens 505-2557 Manual De Usuario
Installation
2-5
SIMATIC 505–2557 Installation and Operation Guide
Locate the temperature scaling jumper JP66 on the right hand side of the
module (See Figure 2-2) and select either degrees Fahrenheit or Celsius by
positioning the jumper in the DEG F or DEG C position.
module (See Figure 2-2) and select either degrees Fahrenheit or Celsius by
positioning the jumper in the DEG F or DEG C position.
Locate JP90 on the printed circuit board (See Figure 2-2). Select DISABLE
to present data to the PLC as temperature X10 or millivolts X100. Select
ENABLE to scale and present the data as an unsigned integer from
0–32000.
to present data to the PLC as temperature X10 or millivolts X100. Select
ENABLE to scale and present the data as an unsigned integer from
0–32000.
Figure 2-1
Factory Configuration Jumper Settings
NOTE: In the sample chart above the standard shipping configuration is
indicated as 3 wire 100
indicated as 3 wire 100
Pt, 16 WX, filtering enabled, degrees C and scaling
disabled.
Selecting Degrees
Celsius or
Fahrenheit
Celsius or
Fahrenheit
Selecting Data
Scaling
Scaling