Error Messages
ERROR MESSAGES
Temp
Setpoint
Cycle
75% SP
Start
TUNE
TUNE
Tuning
DAC
PID
New PID
values
entered
Time
(100% output)
oS 1
oS 2
Ct A
Ct b
Ct 3
Ct 4
uS
Ct 1
Ct 2
SENSOR FAULT
Upper display alternates: 
inPt 
and 
FAiL
Indicates:   thermocouple burnout RTD/Pt100 open or 
short circuit or negative over-range.
Action:  
Check sensor/wiring
NON-VOLATILE MEMORY ERROR
Upper display alternates: 
dAtA
and 
FAiL
Action:  
De-power briefly. Replace unit if problem 
persists
MANUAL POWER ERROR
Upper display alternates: 
hAnd 
and 
FAiL
SP1 set to ON/OFF in 
CYC.t
Action:      Select proportional mode
IMMEDIATE FAIL ON AUTOTUNE START
Upper display alternates: 
PV tunE 
and 
FAiL
Lower display 0
1. No setpoint entered. 
Action:      Enter setpoint
2. SP1 set to ON/OFF in
Action:      Select proportional mode
Note:
To reset and clear error press ▲▼ together 
briefly to cancel message.
FAIL LATER DURING AUTOTUNE CYCLE
The thermal characteristics of the load exceed the 
Autotune algorithm limits. The failure point indicated 
by any display 0.0 in
e.g. Ctb = 0.0 see adjacent diagram.
Action:
1.
Change the conditions. eg. raise setpoint
2.
Try
3.  Check SP1.P percentage power 
(see IMPROVING CONTROL ACCURACY)
4.  If the error message persists, call CAL 
for advice.
READING AUTOTUNE TUNING CYCLE 
RESULTS IN
tECh
1. Index to
release ▲ or ▼, lower display will alternate 
Ct.A
and value
2. Keep ✱ pressed and press ▲ once, the lower 
display will alternate 
Ct.b 
and value (eg. 19.6) 
3. Repeat step 3 above to view:
Ct 1, Ct 2, Ct 3, Ct 4, oS 1, uS
and
oS 2
.
Autotune tuning data and limits
14
INPT
DATA
HAND
FAIL
0
CYC.T
ON.OF
TECH
TUNE
AT.SP
TECH
CT.A