Step 2: Wire the Digital I/O 
Form C Digital Output: Mechanical Alarm Relay
Form C Digital Output: Solid State Relay Outputs DO1 - DO4
Form A Digital Outputs: Solid State Relay Outputs DO5 - DO12
Digital Inputs: Solid State DI1 - DI3 
C
AUTION
Field Hi-Pot testing to the above isolation levels is not recommended -- risk
of meter damage.
Contacts
common, NO, NC
Max. Switching Voltage
250 VAC/125 VDC (internally limited to 300 V peak)
Max. Switching Current 1 A AC/0.1 A DC
Operate Time (max.)
8 ms
Release Time (max.)
4 ms
Isolation to Ground
2,000 VAC for 60 s (50 Hz)
Rating
Installation category II (local), Pollution degree 2
Minimum Operations
5,000,000
Excitation
External only
Contacts
common, NO, NC
Max. Switching Voltage 250 VDC/ 210 VAC (internally limited to 350 V peak)
Max. Switching Current 100 mA AC/DC
Isolation to Ground
2,000 VAC for 60 s (50 Hz)
Rating
Installation category II (local), Pollution degree 2
Excitation
External only
Max. Switching Voltage 250 VDC/ 210 VAC (internally limited to 350 V peak)
Max. Switching Current 100 mA AC/DC
Isolation to Ground
2,000 VAC for 60 sec. (50 Hz) 
Rating
Installation category II (local), Pollution degree 2
Excitation
External only
Minimum Pulse Width
1 ms
Maximum Pulse Rate
20 Hz
Timing Resolution
1 ms
Updated
½ cycle (does not affect timing resolution)
Isolation to Ground and to 
Contacts
2,000 VAC for 60 sec. (50 Hz)
Rating
Installation category II (local), Pollution degree 2
Hi-Voltage Range
75 - 280 VDC or VAC (RMS)
Lo-Voltage Range
15 - 75 VDC or VAC (RMS)
Hi-Voltage Input Impedance
100 kΩ
Lo-Voltage Input Impedance
20 kΩ