INSTALLATION INSTRUCTIONS
69- 1521- 2
C7735A1000 Discharge Air
 Temperature Sensor
APPLICATION
The C7735A1000 Discharge Air Temperature Sensor 
(DATS) is a duct-mounted temperature probe that 
provides capacity control of heating and cooling 
equipment. The DATS is used only with zoning solutions, 
including TZ-3, MABS EZ-2 and MABS EZ-4, and EMM-
3 and EMM-3U control panels. Mounted in the supply air 
duct, the DATS senses the delivered air temperature and 
cuts off the heating or cooling when the delivered air 
temperature goes above or below normal operating 
limits.
When either limit setting is reached, the appropriate heat 
or cool light emitting diode (LED) flashes on the TZ-3 or 
EMM series panels, indicating that heating or cooling is 
shut off. The call still exists and heated or cooled air is 
still being supplied to the calling zones. Once the 
delivered air temperature drops ten degrees for heating, 
or rises ten degrees for cooling, the heating or cooling 
equipment is brought back on. The ten-degree 
differential provides adequate minimum time-off to avoid 
damaging the equipment. EMM series has a 2.5 minute 
timer as equipment protection.
The location of the DATS is critical; it should not be 
placed in line-of-sight of the heat exchanger or cooling 
coil because the DATS could activate prematurely. It 
should also be located before the bypass damper, when 
applicable. DATS dimensions are shown in Fig. 1. 
The DATS requires only two wires. Normal 18 to 22 
gauge thermostat wire is used for shorter runs. For 
longer runs or when wiring near voltage, shielded cable 
is used.
Fig. 1. C7735A dimensions in in. (mm).
INSTALLATION
When Installing this Product...
1.
Read these instructions carefully. Failure to follow 
them could damage the product or cause a hazard-
ous condition. 
2.
Check the ratings given in the instructions and on 
the product to make sure the product is suitable for 
your application. 
3.
Installer must be a trained, experienced service 
technician.
4.
After completing installation, use these instructions 
to check out the product operation.
IMPORTANT
Do not locate the DATS probe in a duct near the 
heat exchanger or strip heat, which can cause 
false temperature readings.
1.
Locate the DATS on the supply trunk between the 
bypass damper and the evaporator coil and/or heat 
exchanger. If a bypass damper is not used, locate 
the DATS between the zone dampers and the 
evaporator coil and/or heat exchanger. See Fig. 2.
Fig. 2. DATS mounting location.
M14926
4-1/8 (102)
3-7/8
(77)
3-3/4
(77)
1-1/4
(25)
ZONE DAMPERS
BY PASS DAMPER
PLACE SENSOR 
INTHIS AREA.
DO NOT
PLACE
SENSOR IN
THIS AREA.
M14877
EVAPORATOR COIL
HEAT EXCHANGER
BLOWER