Hitachi SJ300-037HFE Manual De Usuario

Descargar
Página de 289
SJ300 Inverter
Configur
ing Dr
iv
P
a
ra
met
e
rs
3–39
Function 
Code
Data
Resulting Non-displayed 
Functions (when B37 = 01)
Notes
C021 – C025, 
C026
02, 06
C042, C043
Frequency arrival signal
03
C040, C041
Overload advance notice
07
C055 – C058
Over-torque
21
C063
Zero-speed detection signal
24, 25
C045, C046
Frequency arrival signal
26
C011
Overload advance notice 2
H002
00
H020 – H024
Motor constant
01, 02
H030 – H034
Motor constant (auto-tuning)
H202
00
H220 – H224
Motor constant
01, 02
H023 – H0234
Motor constant (auto-tuning)
P010
01
P011 – P023, P025 – P027
Expansion card function
“B” Function
Run 
Mode
Edit
Lo Hi
Defaults
Units
SRW Display
Func.
Code
Name
Description
–FE
(CE)
–FU
(UL)
–FR
(Jpn)
B040
Torque limit selection
Five option codes:
00 4-quadrant mode
01 Selected by 2 input 
terminals (see p. 
)
02 From analog [O2] input 
(0 to 10V = 0 to 200%)
03 From expansion card 1
04 From expansion card 2
✘ ✔
00
00
00
>b040 TRQ-LIMIT
Mode       4-SET
B041
Torque limit (1) 
(forward-driving in 4-
quadrant mode) 
Range is 0 to 200%
(torque limit disabled)
✘ ✔ 150. 150. 150.
%
>b041  RQ-LIMIT
LEVEL1      150%
B042
Torque limit (2) 
(reverse-regenerating in 
4-quadrant mode)
Range is 0 to 200%
(torque limit disabled)
✘ ✔ 150. 150. 150.
%
>b042 TRQ-LIMIT
LEVEL2      150%
B043
Torque limit (3) 
(reverse-driving in 4-
quadrant mode)
Range is 0 to 200%
(torque limit disabled)
✘ ✔ 150. 150. 150.
%
>b043 TRQ-LIMIT
LEVEL3      150%
B044
Torque limit (4) 
(forward-regenerating 
in 4-quadrant mode)
Range is 0 to 200%
(torque limit disabled)
✘ ✔ 150. 150. 150.
%
>b044 TRQ-LIMIT
LEVEL4      150%
B045
Torque limit LADSTOP 
enable
Temporarily stops accel/
decel ramps during torque 
limit. Available for SLV, 0 
Hz domain, or vector control 
with feedback mode.
Two option codes:
00 Disable
01 Enable
✘ ✔
00
00
00
>b045 TRQ-LIMIT
SELECT       OFF