Optional Controlled Decel and Alarm at Power Loss
Oper
ations
a
nd Moni
tor
ing
4–6
The timing diagram below shows a power loss scenario and the related parameter settings. 
During the controlled deceleration the inverter itself acts as a load to decelerate the motor. With 
either a high-inertia load or a short deceleration time (or both), it is possible that the inverter 
impedance will not be low enough to continue linear deceleration and avoid an over-voltage 
condition on the DC bus. Use parameter B052 to specify a threshold for the over-voltage. In 
this case, the inverter pauses deceleration (runs at constant speed). When the DC bus decays 
again below the threshold, linear deceleration resumes. The pause/resume process will repeat as 
necessary until the DC bus energy is depleted (under-voltage condition occurs).
NOTE: (1) Be sure to set the over-voltage threshold greater than the DC bus voltage trigger 
level
 (B052 > B051) for proper operation.
(2) Once the power loss deceleration function starts, it will complete and stop the motor even if 
input power is restored. In that case, it automatically enables the Run mode again.
DC bus (V)
Output
Frequency
Under-voltage 
level
B052
B051
B054
B053
t
t
0
0