Hitachi hitachi series inverter Manual De Usuario

Descargar
Página de 99
 
47 
“d” Function 
Func. 
Code 
Name 
Description 
Run 
Mode 
Edit 
Units 
D006 
Intelligent output 
terminal status 
Displays the state of the intelligent 
output terminals: 
 
 
 
 
 
 
− 
− 
D007 
Scaled output frequency 
monitor 
Displays the output frequency scaled 
by the constant in B086. 
Decimal point indicates range: 
0 to 3999 
− 
Hz times 
constant 
d008 
Actual frequency monitor 
Displays the actual frequency, range 
is -400 to 400 Hz 
− 
Hz 
d009 
Torque command monitor 
Displays the torque command, range 
is -200 to 200 % 
− 
d010 
Torque bias monitor 
Displays the torque bias value, range 
is -200 to 200 % 
− 
d012 
Output torque monitor 
Displays  the output torque, range is 
-200 to 200 % 
− 
D013 
Output voltage monitor 
Voltage of output to motor, 
Range is 0.0 to 600.0V 
− 
d014 
Input power monitor 
Displays the input power, range is 0 
to 999.9 kW 
− 
KW 
d015 
Watt-hour monitor 
Displays watt-hour of the inverter, 
range is 0 to 9999000 
− 
 
D016 
Elapsed RUN time monitor 
Displays total time the inverter has 
been in RUN mode in hours. 
Range is 0 to 9999 / 1000 to 9999 / 
⎡100 to ⎡999 (10,000 to 99,900) 
− 
hours 
D017 
Elapsed power-on time 
monitor 
Displays total time the inverter has 
been powered up in hours. 
Range is 0 to 9999 / 1000 to 9999 / 
⎡100 to ⎡999 (10,000 to 99,900) 
− 
hours 
D018 
Heat sink temperature monitor 
Temperature of the cooling fin, range 
is -20~150 
− 
°C 
d022 
Life 
check 
monitor 
Displays the state of lifetime of 
electrolytic capacitors on the PWB 
and cooling fan. 
 
 
 
 
 
− 
− 
d023 
Program counter monitor 
[EzSQ] 
Range is 0 to 1024 
− 
− 
d024 
Program number monitor 
[EzSQ] 
Range is 0 to 9999 
− 
− 
d025 
User monitor 0 
[EzSQ] 
Result of EzSQ execution, range is 
–2147483647~2147483647 
− 
− 
d026 
User monitor 1 
[EzSQ] 
Result of EzSQ execution, range is 
–2147483647~2147483647 
− 
− 
d027 
User monitor 2 
[EzSQ] 
Result of EzSQ execution, range is 
–2147483647~2147483647 
− 
− 
Lifetime expired 
Normal 
Electrolytic caps 
Cooling fan
ON
OFF 
 
 
 
 
Relay 12 11