Outback Power Systems GFX1548 Manual De Usuario

Descargar
Página de 40
Installation
 
900-0113-01-00 Rev A 
19
 
DC Wiring
     
 
 
 
CAUTION:  Equipment Damage 
Never reverse the polarity of the battery cables.  Always use correct polarity. 
 
CAUTION:  Fire Hazard 
Always install a breaker, fuse, or protective device to protect the DC system.  
Table 4 
DC Conductor Size and Torque Requirements
      
 
Inverter   Nominal DC Amps
(Derated 125%)
 
Conductor Size  
(Minimum)
 
Breaker Size 
GFX1312 
130 
2/0 AWG or 0.105 in2 (70 mm2) 
175 Adc 
GFX1424 
70 
1/0 AWG or 0.083 in2 (70 mm2) 
125 Adc 
GFX1548 
37.5 
#1 AWG or 0.066 in2 (50 mm2) 
100 Adc 
Terminal Location 
Torque Requirements 
Inverter DC Terminals
 
35 in-lb (4.0 Nm) 
Battery Terminals
 
See battery manufacturer’s recommendations 
When installing DC cables: 
  Note minimum sizes in Table 4, but refer to local codes for absolute cable size recommendations. 
  Battery positive and negative cables should be no longer than 10 feet (3 meters) each, to minimize voltage 
loss and other effects. 
  Always install breakers or fuses on the positive cable. 
  The cables listed above are for each inverter in a system.  In a system with multiple inverters, each inverter 
requires its own cables and breakers of the size indicated. 
  The inverter’s battery terminal is a threaded stud which accepts a ring terminal lug.   Use crimped and sealed 
copper ring lugs with 5/16 in (0.79 cm) holes, or use compression lugs. 
  Tie, tape, or twist cables together to reduce self-inductance.  Run positive and negative cables through the 
same knockouts and conduit. 
  Make certain the DC breaker is turned to the off position, or the fuse is removed, before proceeding. 
 
 
If present, remove the battery 
terminal covers.  These are made of 
stiff plastic with a snap-on design.  
Remove carefully using a flat 
screwdriver inserted into the slots 
on the sides of each cover. 
Figure 8 
Battery Terminal Covers