Troubleshooting Reference Chart
PROBLEM/
SYMPTOM
PROBABLE
CAUSE
LOCATION
REASON - CORRECTION
Ionizing Section of Cell
1.  Dirty insulator(s) – Clean
2.  Defective insulator(s) – Replace
3.  Foreign Object Between Ionizing Bar
and Ground electrode - Remove
Collecting Section of Cell
1.  Dirty insulator(s) - Clean
2.  Defective insulator(s) – Replace
3.  Foreign Material Bridging Plates -
Remove
4.  Bent Plates – Straighten or Replace
High Voltage Leads
1.  Disconnected High Voltage Lead
Contacting Ground - Reconnect
2.  Defective Lead/Insulation Breakdown
– Replace Entire Lead
Indicating Light Not
Glowing
Short Circuit
Power Supply
Charred/Over Heated Components –
Replace Power Supply
Control
1.  Disconnected Supply Line Power –
Reconnect
2.  Faulty indicting Light - Replace
Power Supply
1.  Disconnected Wire – Resolder
2.  Charred/Over Heated Components –
Replace Power Supply
Indicating Light Not
Glowing
Open Circuit
Electronic Air Cleaner Housing
1.  Electrical Interlock Switch Not Closed
– Close Access Door
2.  Junction Box interlock switch not
closed – Secure Cover
3.  Faulty Electrical Interlock Switch -
Replace
Indicating Light
Flickering
High Resistance Short
High Voltage Circuit
1.  Ionizer High Voltage Lead Connected
to Plate Section and Plate Lead to
Ionizer – Reconnect Leads
2.  Loose or Disconnect high Voltage
Lead-Tighten or Reconnect
3.  Loose or Defective Intercell
Connection (on Multicell Units) –
Tighten or Replace
4.  Foreign Object Adrift in Ionizer or
Plate Section of Cell – Remove
5.  Clean cells and replace in unit.
Loss In Capturing
Velocity
Restriction In Air
Flow
Modular Sections
1.  Metal Mesh Filters Dirty – Clean
2.  Bag Filter Saturated - Replace
Loss in Collecting
Efficiency
Disconnected
Components
Electronic Air Cleaner
1.  Disconnected high Voltage Lead -
Reconnect
2.  Cell(s) in Multicell Unit Not Connected
– Repair or Replace Intercell High
Voltage Connectors
Loss in Odor Control
Decrease In
Adsorption Ability
Adsorber Module
1.  Saturated Activated Carbon –
Replace with New or Refurbished
Panels