GE 994-0089 Manual De Usuario

Descargar
Página de 92
 GE 
Energy 
 
D400 Substation Data Manager User's Manual  
37
 
IRIG-B Input Adapter 
 
Switch SW2 Configuration 
Switch SW2 controls the signal option for the selected state option (SW1). It contains 
three switch positions that can be set to ON or OFF to select the appropriate signal. 
IRIG-B Input Card Switch SW2 Settings 
SW2 Switch Positions 
Input Signal Option 
1 2 3 
Fiber Optic (RX) 
ON 
OFF 
OFF 
TTL (TB1) (default) 
OFF 
ON 
OFF 
BNC (J2) 
OFF 
OFF 
ON 
 
Switch SW3 Configuration 
Switch SW3 controls the state option for the IRIG-B fiber optic TX input. It contains two 
switch positions that can be set to ON or OFF to select the appropriate state. 
IRIG-B Input Card Switch SW3 Settings 
SW3 Switch Positions 
Fiber Optic TX Option 
1 2 
Fiber RX (default) 
ON 
OFF 
Inverted OFF 
ON