National Instruments USB-6008/6009 Manual De Usuario

Descargar
Página de 25
USB-6008/6009 User Guide and Specifications
14
ni.com
Connecting Analog Output Loads
To connect loads to the USB-6008/6009, connect the positive lead of the 
load to the AO terminal, and connect the ground of the load to a GND 
terminal. 
Figure 11.  Connecting a Load
Minimizing Glitches on the Output Signal
When you use a DAC to generate a waveform, you may observe glitches in 
the output signal. These glitches are normal; when a DAQ switches from 
one voltage to another, it produces glitches due to released charges. The 
largest glitches occur when the most significant bit of the DAC code 
changes. You can build a low-pass deglitching filter to remove some of 
these glitches, depending on the frequency and nature of the output signal. 
Refer to 
ni.com/support
 for more information about minimizing 
glitches.
Digital I/O
The USB-6008/6009 has 12 digital lines, P0.<0..7> and P1.<0..3>, which 
comprise the DIO port. GND is the ground-reference signal for the DIO 
port. You can individually program all lines as inputs or outputs. 
Digital I/O Circuitry
Figure 12 shows P0.<0..7> connected to example signals configured as 
digital inputs and digital outputs. You can configure P1.<0..3> similarly.
USB-6008/6009
GND
AO
Load