4200FA XT1  
 
 
September 6, 2004
 
 
5
 
 
 
 
 
+/- 3% (loss or return of input power) 
     +/- 
8% 
(bypass 
to 
inverter) 
13) Transient Voltage Recovery  50ms maximum to within 2% of nominal 
14) Overload Cap. (on inverter)  125% for 90 sec., 150% for 30 sec. 
15) Overload Cap. (on bypass) 
1000% for 10ms, 125% for 10 min. 
16) Crest Factor 
 
 
3.0 
17) Harmonic Voltage Distortion  1.5%  THD  maximum,  1%  maximum  for 
any single harmonic (linear load) 
18) Inrush Current Protection 
Automatic transfer to bypass, then auto-  
 
 
 
 
 
return to inverter ( retransfer may be  
     inhibited 
by 
jumper) 
19) Output Overcurrent  
 
Hall-Effect  Current  Transformer  and 
Fusing 
 
C. Batteries 
 
1) a. Battery Type:      Sealed, Valve Regulated Lead Acid cells 
     b. Flooded Type:   Wet Cell Jars 
 
 
2) Protection Time:     10 minutes to 40 hours back-up time @ 50 kVA 
 
 
 
 
 
3) DC Voltage Range:  
UPS Capacity 
50 kVA 
Nominal Voltage 
288 VDC 
Alarms Voltage(V low) 
252 VDC 
Shutdown Voltage (V min) 
216 VDC 
 
 
 
 
 
4) Ripple Voltage: 2% RMS maximum 
 
D. Environmental 
 
1) Efficiency: 88.5% (AC/AC); 90% (DC/AC) 
2) Operating Temperature: UPS: 32 to 104
° F (0 to 40° C) 
     
Battery: 
68 
to 
77
° F (20 to 25° C) 
3) Storage Temperature:   UPS:     -4 to 140
° F (-20 to 60° C)  
 
 
 
 
 Battery: prolonged storage above 104
° F 
 
 
 
 
(40
° C) causes rapid battery degradation  
 
4) Relative Humidity: 30-90% (non-condensing) 
5) Audible Noise:   ~63 dB (‘A’ scale @ 1 meter 
6) Altitude: < 6,000-ft. maximum (< 2,000 m)