11-7
Cisco ONS 15454 Installation and Operations Guide
November 2001
Chapter 11      SNMP
SNMP Traps
is service affecting or non-service affecting. The traps also contain a date/time stamp that shows the date 
and time the alarm occurred. The ONS 15454 also generates a trap for each alarm when the alarm 
condition clears.
Each SNMP trap contains ten variable bindings listed in 
The ONS 15454 supports the generic and IETF traps listed in 
Table 11-3
SNMP Trap Variable Bindings
Number
Name
Description
1
cerentGenericAlarmTable
This table holds all the currently-raised alarms. 
When an alarm is raised, it appears as a new entry in 
the table. When an alarm is cleared, it is removed 
from the table and all the subsequent entries move 
up by one row.
2
cerentGenericAlarmIndex
This variable uniquely identifies each entry in an 
alarm table. When an alarm in the alarm table clears, 
the alarm indexes change for each alarm located 
subsequent to the cleared alarm.
3
cerentGenericAlarmObjectType
This variable provides the entity type that raised the 
alarm. The NMS should use this value to decide 
which table to poll for further information about the 
alarm.
4
cerentGenericAlarmSlotNumber
This variable indicates the slot of the object that 
raised the alarm. If a slot is not relevant to the alarm, 
the slot number is zero.
5
cerentGenericAlarmPortNumber
This variable provides the port of the object that 
raised the alarm. If a port is not relevant to the 
alarm, the port number is zero.
6
cerentGenericAlarmLineNumber
This variable provides the object line that raised the 
alarm. If a line is not relevant to the alarm, the line 
number is zero.
7
cerentGenericAlarmObjectIndex
Every alarm is raised by an object entry in a specific 
table. This variable is the index of the objects in 
each table; if the alarm is interface related, this is 
the index of the interfaces in the interface table.
8
cerentGenericAlarmType
This variable provides the exact alarm type.
9
cerentGenericAlarmState
This variable specifies alarm severity and 
service-affecting status. Severities are minor, major 
and critical. Service- affecting statuses are 
service-affecting and non-service affecting.
10
cerentGenericAlarmTimeStamp
This variable gives the time when the alarm 
occurred. The value is the number of the ticks that 
has lapsed since 1/1/1970.