GE 2300 V Manual De Usuario

Descargar
Página de 266
3-66  
••••
  Chapter 3  Paramters/Functions
Innovation Series Medium Voltage GP Type - G Drives GEH-6385
Motor Ground Protection
The Motor Ground Protection function detects a ground fault condition in the motor
phases. The function is automatically configured by the control; no user
configuration is necessary.
Function inputs
The following table specifies the input variables of the Motor Ground Protection
function.
Variable
Description
DC neut volt mag
Absolute value of the DC bus neutral voltage
Function outputs
The following table specifies the output variables of the Motor Ground Protection
function.
Variable
Description
Gnd cur signal
Ground current indication (filtered).  Note that this value may
actually be scaled as the voltage sensed by the BICM, not a
current.  If Gnd signal scl is 1.0, this is the sensed voltage.
Gnd flt warning
This variable is used external to this function to indicate that the
alarm, Ground flt alm, LP is present.
Gnd flt trip
This variable is used external to this function to indicate that the
fault, Gnd flt trip is present.
LP fuse stat
This signal, when True, indicates that the value LP fuse blown
sel
 points to is True.  When Detector mode is set to Disable, this
variable will always be True.
Function configuration
The following table specifies the configuration parameters of the Motor Ground
Protection
 function. The control sets these parameters automatically; they should not
be changed except in unusual circumstances.
Parameter
Description
Detector mode
When set to Enable, the Motor Ground Protection function is
enabled. The Ground flt alm, LP alarm and Gnd flt trip trip
fault will be annunciated if a ground fault condition occurs.
When set to Disable, neither the alarm nor fault will occur.
The default is Enable.
Gnd signal sel
Pointer to the ground fault signal.  It points by default to
parameter DC neut volt mag.
Gnd signal scl
Voltage to current scale factor which is applied to the input
analog signal pointed to by Gnd signal sel. This parameter is
set to 1.0 as default, leaving the scaled signal output as a
voltage.
Gnd signal alarm on
The level at which the Ground flt alm, LP alarm is present.
Gnd signal alarm off
The level at which the Ground flt alm, LP alarm clears.
Gnd signal trip lvl
The level at which the Gnd flt trip trip fault occurs.
Gnd signal fil
The bandwidth of the low pass filter (Radians/second) applied
to the analog input signal pointed to by Gnd signal sel.
LP fuse blown sel
Pointer default setting is MOV fuse OK status.