InRow RC Installation
A-Link ports
Note: All input and output connections should be wired as Class 2 circuits.
Depending on the equipment configuration, additional control connections may be required for the
A-Link remote communications through APC Network Management Card support or other equipment-
monitoring software. A special RJ-45 terminator is provided and must be installed if both A-Link ports
are not otherwise used, as shown.
A-Link remote communications through APC Network Management Card support or other equipment-
monitoring software. A special RJ-45 terminator is provided and must be installed if both A-Link ports
are not otherwise used, as shown.
Active flow controllers (AFC).
If AFC units are installed in the row, they are connected to the A-Link
bus as shown.
See the AFC Installation manual for more information.
1
RJ-45 terminator (provided)
2
A-Link cable
na22
43
a
First InRow RC
Second InRow RC
Last InRow RC
AFC
AFC