Siemens M7-400 Manual De Usuario

Descargar
Página de 638
Analog Modules
5-115
S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07
Table 5-64 Parameters of the SM 431; AI 16 
 
 16 Bit, continued
Parameter
Scope
Parameter
Type
Default
2)
Value Range
Measurement
Measuring type
Disabled
U
Voltage
4DMU
Current
(4-wire transmitter)
2DMU
Current 
(two-wire transmitter)
R-4L
Resistor 
(four-conductor terminal)
R-3L
Resistor 
(three-conductor terminal)
RTD-4L Thermal resistor
(linear, four-conductor 
terminal)
RTD-3L Thermal resistor
(linear, three-conductor 
terminal)
TC-L
Thermocouple (linear)
U
Static
Channel
Measuring range
Refer to Section 5.22.2 for the
measuring ranges of the input
channels that you can set.
"
10 V
teference
Temperature
– 273.15 to 327.67 
o
C
0.00 
o
C
Interference
suppression
400 Hz; 60 Hz; 50 Hz
50 Hz
Smoothing
None
Low
Average
High
None
Dynamic
Module
Ref. junction
None
RTD on Channel 0
Reference temperature value
None
1)
If you use the module in ER-1/ER-2, you must set this parameter to “No” because the interrupt lines are
not available in ER-1/ER-2.
2)
Only in the CC (central controller) is it possible to start up the analog modules with the default settings.
A Point to Note About Channels for Hardware Interrupts with the End of Scan
Cycle Trigger
You can parameterize hardware interrupts for the end of scan cycle for one of the
16 channels because the module can only trigger these interrupts on one channel.