Package Contents 
•  MED100A Industrial Serial To Multi-mode Fiber Optic 
Converter 
• Datasheet 
•  Fiber Optic Dust Cover (installed) 
Front Panel 
Fiber Connectors 
Multi-mode, ST Connectors 
PWR LED 
ON When Power Applied 
TD LED 
On When Serial Data Transmitted 
RD LED 
On When Serial Data Received 
DIP Switch 
8 Position, 
Terminal Blocks 
Serial Data and Power 
DIN Rail Mounting 
1.  Angle the converter DIN clip over the top of the DIN 
rail.  
2.  Move the converter so that it is parallel with the DIN 
Rail and snap the DIN clip into place.. 
DIP Switch (SW1) 
Pos ON 
OFF 
RS-422/485 Baud Rate Selection 
RS-422/485 Baud Rate Selection 
RS-422/485 Baud Rate Selection 
RS-422/485 Baud Rate Selection 
RS-422/485 Baud Rate Selection 
FO Multi-drop Ring 
FO Point-to-Point 
RS-422/485 Mode Selection 
RS-422/485 Mode Selection 
 
Terminal Block 
Terminal Signal 
RS-232 RD (OUTPUT) 
GND 
GND 
RS-232 TD (INPUT) 
NOT CONNECTED 
+10 TO 30 VDC 
RS-422/485 TDA(-) / DATA A(-) 
RS-422/485 TDB(+) / DATA B (+) 
+10 TO 30 VDC 
RS-422/485 RDA(-) / DATA A (-) 
RS-422/485 RDB(+) / DATA B (+)  
RS-422/485 Baud Rate / 
Timeout 
Baud 1 2 3 4 5  R9 
TIME 
OUT 
1200  ON  OFF OFF OFF OFF 820 
kΩ 8.20 
ms 
2400  ON  OFF OFF OFF OFF 430 
kΩ 4.30 
ms 
4800  OFF OFF OFF OFF ON  None  2.20 
ms 
9600  OFF OFF OFF ON  OFF None  1.30 
ms 
19.2K  OFF OFF ON  OFF OFF None  0.56 
ms 
38.4K  OFF ON  OFF OFF OFF None  0.27 
ms 
57.6K  ON  OFF OFF OFF OFF None  0.22 
ms 
76.8K  ON OFF ON ON OFF None  0.14 
ms 
115.2 
ON ON ON OFF OFF None  0.10 
ms 
153.6K ON  OFF OFF OFF OFF 6.2 
kΩ 0.06 
ms 
230.4K ON  OFF OFF OFF OFF 4.3 
kΩ 0.04 
ms 
460.8K OF  OFF OFF OFF OFF 2.2 
kΩ 0.02 
ms 
The Dip-Switch on the MED100A defines the mode of operation 
when being used for RS-422 or RS-485. Positions 1 through 5 
determine the timeout of the RS-485 driver. Because the driver is 
controlled by hardware, a specific time must be set to tell the 
hardware how long to wait for data on the fiber side before turning 
off the RS-422/485 driver. If this time is set too short, the driver 
could be disabled before transmission is complete, resulting in 
data corruption. If the time is set too long, the device may respond 
before the RS-422/485 driver in the MED100A is disabled, 
corrupting this response. Set the timeout for approximately one 
character time or longer. The character times for several different 
baud rates are selectable on switch positions 1 through 5. If you 
need a different timeout than what is provided, R10 can be 
removed and replaced with a different value R9. This table shows 
different timeout values for the switch positions as well as R9 
replacement values.