Cisco ASR 9001 and Cisco ASR 9001-S Routers Hardware Installation Guide
OL-26701-02
Chapter 1      Preparing for Installation
Site Requirement Guidelines
Figure 1-18 AC Power Cord CAB-9K10A-EU
Figure 1-19 AC Power Cord SFS-250V-10A-IS
DC Powered Router
Connections to DC power modules are rated at 20 A maximum. The system accepts a nominal input voltage 
of –48 VDC with an operational tolerance range of –48 VDC to –60 VDC. One dedicated, commensurately 
rated DC power source is required for each power module connection.
Power connections to the each DC power module requires two cables: one source cable and one return 
cable. 
For DC power cables, we recommend that you use 20-A-rated, high-strand-count copper wire cables. 
The length of the cables depends on your router location from the source power. 
Note
DC power cables are not available from Cisco, but they are available from external commercial cable 
vendors.
You must terminate DC power cables using terminal blocks. The terminal blocks are supplied along with 
the DC power supply modules from Cisco. The terminal block part number is PC 5/2-STF-7.62 BD:+,- 
from Phoenix contact. 
Connector: WS 002 
Cordset rating: 10A, 250 V
Length: 8 ft 2 in. (2.5 m)
Plug:
M2511
33
2625
Cordset rating: 10 A, 250V 
Length: 8 ft 2 in. (2.5 m)
Plug:
EL 212
(SI-32)
33
2624
Connector: WS 002