4. Properties 
 
 
 
 
 
 
          Vlinx MESR9xx Modbus Gateway 
 
Page 27 
                                                                                                                                           
Manual Documentation Number MESR9xx-4508m 
www.bb-elec.com/
 
www.bb-europe.com/
 
 
Password 
When you first receive the MESR9xx Modbus gateway from the factory the Password is 
blank so that you can initially access the Modbus gateway without entering a value into 
this field. To ensure security you should create and save a password the first time you 
configure the Modbus gateway. After a password has been set up it must be entered each 
time you login to Vlinx Manager. The password is used to access the configuration pages 
from the Vlinx Manager Login page and can be changed from the General page. 
 
Port# ID Remap 
This allows the gateway to remap the Modbus ID to another ID on the serial port.  This 
would be used when there are two identical Modbus serial networks talking to Modbus 
TCP controllers.   
The first box is the staring ID of a range you want to remap; the second box is the last ID 
of that range.  If you are just remapping one ID the second box is not filled in.  The third 
box is the start of the remap range on the serial port.  The fourth box will auto fill in 
based on the range filled in the first 2 boxes.  The range must check to make sure it is a 
valid range, and does not overlap with any of the other ranges set.  Up to 5 address ranges 
can be remapped per port.   
The default will have all the check boxes unchecked, and all fill in boxes blank. 
 
Serial Interface Modes 
Four serial interface modes of operation are: 
•  RS-232 - Point-to-point serial communications connection used by PC COM ports 
and many other systems. Capable of baud rates up to 115.2 kbaud over short 
distances (typically 50 feet). Typically uses DB-9 connectors but terminals are 
also used on MESR9xx Modbus gateways. 
•  RS-422 - Point-to-point communications using a transmit pair and a receive pair. 
RS-422 can operate at higher speeds and longer distances than RS-232. Typically 
uses two shielded twisted pairs and screw terminals but DB-9 connectors are also 
used on MESR9xx Modbus gateways. 
•  RS-485 2-wire - Similar speed and distance specifications as RS-422 but allows 
multidrop connections. Typically uses one shielded twisted pair and screw 
terminals but DB-9 connectors are also used on MESR9xx Modbus gateways.