Modbus Basics
 
Manual Documentation Number: Zlinx485m-1808 
www.bb-elec.com
 
www.bb-europe.com
  
stored as 1xxxx (coil) addresses; analog inputs are converted to 12 bit binary values and 
stored in 3xxxx (input register) addresses. 
To configure the Zlinx 485 for Modbus mode: 
1.  Select the Configuration tab. 
2.  Select the Modbus option button. 
3.  In the Modbus Address box, type the Modbus address to be used. Modbus address 0 
is reserved for master systems that do not support broadcasts. 
The allowable range of Modbus addresses is from 1 to 247. The default Modbus 
address is 1. 
 
 
Figure 31. 
Configuration Tab with Default Values 
Testing Modbus Mode Operation 
Using a Modbus base module, a PC and Modbus simulation software (e.g. Modscan) you 
can test the link and hardware, and investigate the operation of the Zlinx 485. Modscan is 
a Windows application that simulates a Modbus master node. You can read from and 
write to memory locations on the Zlinx 485. Modscan is available as a fully functional 
time-limited demo from 
www.win-tech.com
., and more information on the basics of 
Modbus is available at 
www.bb-elec.com