Chapter 5 - Software 
 
 
This chapter will be divided into two sections.  The first section 
covers programming techniques for constructing a command string, 
receiving data and manipulating data in QuickBASIC.  The second 
section discusses how to install and run the demonstration program 
on an IBM PC or compatible. 
 
Programming Techniques 
 
 
This section shows steps and examples of programming the 
485SDD16 in QuickBasic.  If you are programming in another 
language, this section can be helpful as a guideline for programming 
the 485SDD16. 
 
Read I/O Lines Command 
 
The Read I/O Lines command returns two data bytes that 
represents the states of the module's I/O lines.  Refer to this 
command in Chapter 3 for more information. 
Step 1 - Constructing the command string: 
Cmnd$ = "!" + CHR$(Maddr) + "RD" 
Where Maddr is the address of the module that is to return its I/O 
states. 
Step 2 - Transmitting the command string: 
PRINT #1, Cmnd$; 
Step 3 - Receiving the data: 
MSIO$ = INPUT$(1,#1) 
LSIO$ = INPUT$(1,#1) 
Step 4 - Manipulating the data: 
MSIO = ASC(MSIO$) 
LSIO = ASC(LSIO$)
 
Step 5 - Determining an I/O's status: 
MSstatus = MSIO AND mask 
LSstatus = LSIO AND mask
 
By "ANDing" the value of MSIO or LSIO with the appropriate 
mask of an I/O line, the status of the I/O line can be determined.  
If the status is equal to zero the I/O line is LOW. If the status is not 
equal to zero the I/O line is HIGH.  Table 5.1 shows the mask 
values for each I/O line. 
Step 6 - Repeat Step 5 until the status of each I/O line has been  
determined. 
22 485SDD16-1005 
Manual 
B&B Electronics  --  707 Dayton Road  --  Ottawa, IL  61350 
PH (815) 433-5100  --  FAX (815) 433-5104
 
 
Example 5.1 - Determining the status of I/O lines #2 & #10 of 
module #5. 
Maddr = 5 
mask = &H4 
Cmnd$ = "!" + CHR$(Maddr) + "RD" 
PRINT #1, Cmnd$; 
MSIO$ = INPUT$(1,#1) 
LSIO$ = INPUT$(1,#1)
 
MSIO = ASC(MSIO$) 
LSIO = ASC(LSIO$) 
MSstatus = MSIO AND mask 
LSstatus = LSIO AND mask 
If LSstatus equals zero then I/O line #2 is LOW.  If LSstatus is not 
equal to zero then I/O line #2 is HIGH.  If MSstatus equals zero then 
I/O line #10 is LOW.  If MSstatus is not equal to zero then I/O line 
#10 is HIGH. 
 
 
Read Configuration Command 
 
The Read Configuration command reads the module's I/O 
definitions, Power-up states, Address, and Turn-around delay 
respectively.  Refer to this command in Chapter 3 for more 
information. 
Step 1 - Constructing the command string: 
Cmnd$ = "!" + CHR$(Maddr) + "RC" 
Where Maddr is the address of the module that is to return its 
configuration. 
Step 2 - Transmitting the command string: 
PRINT #1, Cmnd$; 
Table 5.1 - Digital I/O Mask Values 
 Mask 
Values 
I/O Line # 
Hexadecimal 
Decimal 
0 & 8 
1H 
1 & 9 
2H 
2 & 10 
4H 
3 & 11 
8H 
4 & 12 
10H 
16 
5 & 13 
20H 
32 
6 & 14 
40H 
64 
7 & 15 
80H 
128